Table 7 - Charge Mode Specifications
MODEL INVC5048H INVC5096H
Nominal Input Voltage
230Vac
Input Voltage Range
180V~ 270Vac (Normal range)
100V~ 270Vac (Generator / Wide Range)
Nominal Output Voltage
Determined by battery type
Nominal Charge Current
20A(95-175V, gen/wide only)
35A(175-275V) @ 35A setting
20A(175-275V) @ 20A setting
10A(95-175V, gen/wide only)
20A(175-275V) @ 20A setting
10A(175-275v) @ 10A setting
Battery initial voltage(sps setup)
>35Vdc
>70Vdc
Charger Short Circuit Protection
Inverter/charger shuts down automatically
Over Charge Protection
Batt.V
≥
60Vdc, Fault,
Buzzer alarm
Batt.V
≥
120Vdc, Fault,
Buzzer alarm
Charge Algorithm
Three stage:
Boost CC (constant current stage)
→
Boost CV (constant voltage stage)
→
Float (constant voltage stage)
Battery Type Setting(±0.3V/batt.)
Battery Type
Boost CC/CV
Float
Voltage(V) Voltage(V)
48 96 48 96
Flooded 58.4 116.8
53.6 108
AGM/Gel 56.4 112.8 54 108
Charger current (+/-10%)
INVC5096H (INVC5048H)