10.0 MECHANICAL DIMENSIONS OF SHELVES
Figure 4 shows the complete mechanical dimensions for the INVR2U-HS and INVR2U-HS-H
shelves. The shelves are identical at 16.38 inches (416mm) deep; with the rear plastic cover
they are 18.00 inches (457mm) deep.
11.0 SAFETY AND INDUSTRY STANDARDS
11.1
The INV2500-HS inverter modules meet the following safety certifications:
STANDARD
AGENCY
UL1950
UL
CSA22.2 No.950
CUL
EN60950
DEMKO
11.2
The INV2500-HS inverter modules are CE marked to indicate conformance to the
European Union’s Low Voltage Directive.
11.3
Input conducted EMI meets FCC20780 part 15J Curve A and EN55022 Curve A.
11.4
Input voice band noise is less than 32dBrnC for a single INV2500-HS with a 240
ampere-hour battery or two INV2500-HSs with a 480 ampere-hour battery.
12.0 OPERATING INFORMATION
12.1
Input Voltage.
These telecom inverters operate off a nominal 48VDC input source which
may be a battery or other DC source. The input voltage range is 42 to 56VDC. Input
connections on the back of the INVR2U-HS shelf are to bus bars with no. 1/4-20 studs.
12.2 Output Voltage.
The output voltage for an INV2500-HS is 115VAC at full load, 120VAC
at no load; for an INV2500H-HS it is 230VAC at full load, 240VAC at no load. See Figure
5(a). Frequency is 50 or 60Hz, ±0.1%. The output voltage has total harmonic distortion
of less than 2.0%. The load current crest factor is 2.8 to 1, and surge capability is up to
300%. The output will drive reactive loads with up to ±90
o
phase angle. The output con-
nectors are screw terminals on the back of the INVR2U-HS shelf.
12.3 Output Power.
Maximum output power for an INV2500-HS module is 115VAC at 22A
RMS or 230VAC at 11A RMS, giving a maximum of 2530 volt-amperes. For two mod-
ules in a shelf it is 115VAC at 44A or 230VAC at 22A, giving a maximum of 5060 volt-
amperes. Exceeding these values may cause electronic shutdown of the output. Full
output power is produced at up to 50
o
C ambient temperature. Above this, output current
must be derated at 2.5%/
o
C. Maximum operating temperature is 70
o
C, at which the out-
put current must be derated by 50%.