SERVICE INSTRUCTIONS FOR THE STAFF
FOR REMOTE CONTROL PANEL IFS7002R
1. Indications of IFS7002R
1. Common indicator for fire condition
2. Common indicator for fault condition
3. Indicator for
System error
4. Indicator for
Fault in power supply
5. Indicator for
Disabled component
6. Test indicator
7. Indicator for
Power supply
8. LCD touch-panel display
∗
1
2
3
4
5
6
7
8
1 2 3 4 5 6 7 8
Fig.1
2. Duty mode
When the control panel is in this condition, only the green LED indicator (Power supply) is
illuminated. The local sounder is switched off.
The logo of the company-producer, information for the current local time and the mode of
operation (DAY or NIGHT) are shown on the panel’s display.
3. Actions of the staff on duty when a signal for fault condition is released
Light indications for various types of faults are shown on Fig. 1. Upon any registered fault
condition the sounder of the fire control panel releases discontinuous signal
.
In the case of Fault condition the indicator
illuminates compulsory and a text message
appears on the display showing the number of the occurred faults. Enter Information and Control Mode
(button
), to reveal on the display all faults. To stop the sound signaling, press the button
(Stop Alarm). Press it once to stop the local sounder of the fire control panel, press it twice to stop the
sounder in the specific remote fire control panel. The button appears on the display when the fire control
panel enters Fault condition and it is deleted when it is pressed or when all fault conditions in each of the
connected fire control panels are removed.
In all other cases when fault condition is signaled press button to stop the sound
signaling and inform the service company.
4. Actions of the staff on duty when a signal for fire condition is released
When a signal for fire condition is released in one or several remote control panels the sounder of the
panel produces discontinuous signal (5 sec sound, followed by 5 sec break) and the indicator
illuminates.
1