Text messages appear on the
display indicating the control panel, the
zone/zones and device/devices, the
time remaining before the control panel
proceeds to Fire condition stage II.
2
In this situation, do the following:
4.1.
Press once button
(Stop
Alarm) to turn off the local sounder of
the control panel, press the button
twice to suppress the sounder of the
remote fire control panel shown
opposite the cursor.
4.2
. Press button
to suppress the activated outputs. When it is pressed a screen appears on the
display requesting a password for Access Level 2 to be entered. To enter password use the buttons with
digits. The length of the password can be 10 symbols maximum. After entering the password, press the
button
. If the password is correct all activated outputs will be switched off.
4.3.
If the protected site is large and you need more time to reach the place of fire indicated by the
repeater, press button
(Inspection). This will add extra time until the respective fire control panel
proceeds to Fire condition Stage II, respectively until the outputs for starting the signaling, blocking and
extinguishing are activated.
4.4.
Check as fast as possible the indicated zones and localized address of the devices for fire condition.
4.5.
Possible options for further actions:
4.5.1.If there is no fire (smoke, heat, flame) and the activation of the fire detector is a “false” one, go
back to the fire control panel as fast as possible and press the rest button
. When it is pressed a
screen appears on the display requesting a password for Access Level 2 to be entered. To enter
password use the buttons with digits. After entering the password, press the button
. If the
password is correct the respective fire control panel will exit Fire condition.
4.5.2. In the case that new “false” activation occurs in the same zone/zones and device/devices, press
button
(Stop Alarm) to stop the sound signaling. If an output is activated press button
to
suppress it. When it is pressed a screen appears on the display requesting a password for Access Level
2 to be entered. To enter password use the buttons with digits. Press button
. If the password is
correct all activated outputs associated to the zone in fire condition will be switched off.
4.5.3. In the case that there is a Fire condition (smoke, heat, flame) activate the closest manual call point
or as fast as possible go back to the fire control panel in Fire condition and press buttons
and
to activate the signaling, blockings and extinguishing. Button
is pressed once or twice until
its graphic display becomes
, indicating that the outputs are activated. Then undertake the
measures stipulated in the Fire Rules at the site in the case of fire.
ATTENTION:
The remote control panel remains in Fire condition until all zones and remote panels
in Fire condition are reset.
FIRE CONDITION
ZONES IN FIRE:
3
>
1 Phase 1 Zone 001 REM #2
Zone 001
3 Phase 1 Zone 002 REM #4
Zone 002
Time Fire Phase2: 115
Time Fire Phase2: 120
Devices in Fire
Total number:
4
1 Loop 01 Zone 001 Addr 001 Object: REM #2
Point 1.001
2 Loop 02 Zone 003 Addr 001 Object: REM #2
Point 2.001
4 Loop 01 Zone 002 Addr 002 Object: REM #4
Point 1.002
Faults total: 00000/0000*
Disables total: 000
Failed Outputs:00000
Disabled Outputs:000
Mode: DAY REP ActInp 0000
11:11:08
Thu 25 Aug 2011