background image

     

Text messages appear on the 

display indicating the control panel, the 
zone/zones and device/devices, the 
time remaining before the control panel 
proceeds to Fire condition stage II. 

 

2

 
       In this situation, do the following: 

4.1. 

Press once button 

 (Stop 

Alarm) to turn off the local sounder of 
the control panel, press the button 
twice to suppress the sounder of the 
remote fire control panel shown 
opposite the cursor.  

 

 

4.2

. Press button 

 to suppress the activated outputs. When it is pressed a screen appears on the 

display requesting a password for Access Level 2 to be entered. To enter password use the buttons with 
digits. The length of the password can be 10 symbols maximum. After entering the password, press the 

button 

. If the password is correct all activated outputs will be switched off.  

4.3. 

If the protected site is large and you need more time to reach the place of fire indicated by the 

repeater, press button 

 (Inspection). This will add extra time until the respective fire control panel 

proceeds to Fire condition Stage II, respectively until the outputs for starting the signaling, blocking and 
extinguishing are activated.  

 

4.4.

 Check as fast as possible the indicated zones and localized address of the devices for fire condition.  

 

4.5. 

Possible options for further actions: 

4.5.1.If there is no fire (smoke, heat, flame) and the activation of the fire detector is a “false” one, go 

back to the fire control panel as fast as possible and press the rest button 

. When it is pressed a 

screen appears on the display requesting a password for Access Level 2 to be entered. To enter 

password use the buttons with digits. After entering the password, press the button 

. If the 

password is correct the respective fire control panel will exit Fire condition. 
4.5.2. In the case that new “false” activation occurs in the same zone/zones and device/devices, press 

button 

 (Stop Alarm) to stop the sound signaling. If an output is activated press button 

 to 

suppress it. When it is pressed a screen appears on the display requesting a password for Access Level 

2 to be entered. To enter password use the buttons with digits. Press button 

. If the password is 

correct all activated outputs associated to the zone in fire condition will be switched off. 
4.5.3. In the case that there is a Fire condition (smoke, heat, flame) activate the closest manual call point 

or as fast as possible go back to the fire control panel in Fire condition and press buttons 

 and 

 to activate the signaling, blockings and extinguishing. Button 

 is pressed once or twice until 

its graphic display becomes 

, indicating that the outputs are activated. Then undertake the 

measures stipulated in the Fire Rules at the site in the case of fire.  

 
 

ATTENTION: 

The remote control panel remains in Fire condition until all zones and remote panels 

in Fire condition are reset.  

FIRE CONDITION 

ZONES IN FIRE:

3

>

 1 Phase 1  Zone 001 REM #2 

    Zone 001 
  3 Phase 1  Zone 002 REM #4 
    Zone 002 

Time Fire Phase2: 115

Time Fire Phase2: 120

 

 

Devices in Fire 

Total number: 

4

  1 Loop 01  Zone 001  Addr 001  Object: REM #2 
    Point 1.001 
  2 Loop 02  Zone 003  Addr 001  Object: REM #2 
    Point 2.001 
  4 Loop 01  Zone 002  Addr 002  Object: REM #4 
    Point 1.002 

 

 

Faults total: 00000/0000* 
Disables total: 000 

Failed Outputs:00000 
Disabled Outputs:000 

Mode: DAY   REP  ActInp 0000

11:11:08

 

Thu 25 Aug 2011

Reviews: