background image

POINT 

OPTICAL-SMOKE 

 

AND

  

HEAT

 FIRE

 

 DETECTOR

TYPE

 

FD 8060

INSTRUCTION MANUAL 0

2

-

806

0

1293

Manufactur

er: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, R. Bulgaria, http://www.unipos-bg.com

TECHNICAL DATA

Power supply

(10-30)V DC

C

urrent consumption in Duty Mode

not more than 120 µA

C

urrent consumption in Fire Condition

- with base type 8000 

or

 8000D

8mA/10VDC; 25mA/30VDC

- with base type 8000R

,

 8000DR

 or 8000L

18mA/10VDC; 55mA/30VDC

Temperature class

À1R (compli

es

 with EN 54-5:2000)

Smoke sensitivity

complies with EN 54-7:2000 + A1:2002

Time to enter Duty mode after power supply is on

up to 40s

Reset time

2s

Time to enter Duty mode after reset

up to 40s

Protected area

circle with 10 m diameter

Height of mounting

up to 8 m

O

utput in Fire Condition

 (

RI/KL terminal

)

for RI 31 or RI 31S

Degree of 

p

rotection

IP 43

Operational temperature range

minus 10°C 

-

 plus 55°C

Relative humidity resistance

(93±3)% at 40°C

Dimensions, base included

Ø100 

mm, h 52mm

W

eight, base included

0,100 kg

Type of connecting 

cable

two-wire

C

ross section

 of the c

onnecting wire

s

(0,8-2,5) mm

2

INSTALLATION

   

 

The fire detector 

operates

 with bases type 

8000

 (standard), 

8000D

 (with Scho

t

tki diode), 

8000R

 (with relay 

output)

,

 

8000DR

  (with  Schot

t

ki  diode  and  resistor  510 

Ù

)  or 

They  are  delivered 

separately and are fixed on the desired place in advance by means of pins and screws. The electrical connection of 
the  components  necessary  for  the  installation  is  done  according  to  the  schematic  diagram  on 

fig.2

.  It  is 

recommended cable shoes to be used.
 

   

The fire detector is placed on the base (fig.1,pos.1).

 

It is rotated clockwise until reaching the guiding grooves 

(fig.1,pos.2). It is rotated until rest (fig.3.1). The slots of the base and the bo

dy

 should match (fig.3.2).

Locking of the fire detector (fig.4).

 Before installation, the key (pos.3) is detached from the base and the rib (pos. 

1) of the locking click 

(pos.2) 

is cut out.

Removing of a fire detector locked to the base.

 Insert the key into the slot (pos.4) push in as in the same time the 

fire detector is rotated anticlockwise. Remove the key and continue to rotate the fire detector in the same direction 
until it is released from the base.

8000

L

  (with  resistor  510 

Ù)

TESTING

    

The fire detector is tested after installation as a part of the site's fire alarm system or 

with

 maintenance activities, 

following this order:
1.

Voltage

 is supplied to the fire

 alarm

 line, to which the tested fire detector is connected from the 

F

ire 

C

ontrol 

P

anel 

or auxiliary power supply unit

 24V DC/0,1A

.

2.After one minute

 is 

activate

d

 the fire detector using a 

S

moke 

Detector Tester 

for the optical part or heat tester for 

the heat part. It should enter Fire condition 

within

 

4

0s.

3.Within 2s is interrupted the supply voltage to the fire alarm line, to which the tested fire detector is connected or a 
reset command is sent from the Fire Control Panel. Fire detector should enter Duty mode and is ready for a new 
activation within 40s.

SERVICE SCHEDULE

     It is done by authorized personnel and includes the following activities:

1.Inspection for visible physical damage

- monthly

2.

T

est

ing

 in real conditions

- monthly

3.*Preventive 

dusting

- every 6 months

*

The  fire  detector  is  removed  from  the  base.  The  body  cover 

(fig.1,pos.6)

  is  removed 

by  rotating  to  rest 

anticlockwise

.

 

T

he  optic  chamber 

cover

  (fig.1,pos.7)  and  the 

screen

  (fig.1,pos.8)

  are  removed.

  For  the  optic 

chamber 

cover

 and the 

screen

 it is permitted washing liquid to be used. Then they should be rinsed out and dried. 

The optic chamber and the thermistor are dusted with a small brush. 

The optic chamber is compulsory dusted 

when  the  fire  detector  enters

 

Contaminated  Chamber  Mode.

  If  it  is  not  cleaned  in  due  time  it  will  get 

contaminated to such an extent that it would not allow the proper functioning of the fire detector which will be 
signaled as Fire Condition.

WARRANTY

  

The warranty period is 36 months from the date of sale.

  

The manufacturer guarantees the normal operation of the fire detector providing that the requirements set herein 

have been observed. 

  

The manufacturer does not bear warranty liabilities for damages

 

caused through accidental mechanical damage, 

misuse, adaptation or modification after production. The manufacturer bears warranty liabilities for damages in the 
fire detector caused through manufacturer's fault only.

GENERAL DESCRIPTION

    The  fire  detector  is  designed  for  early  warning  of  a  fire  condition  responding  to  fixed  threshold  smoke 
concentration or rate of rise temperature or fixed temperature threshold detected in the protected premises. The 
principle of functioning of the optical part is based on infrared rays distraction caused by smoke particles entering 
the optic chamber.

 

The principle of functioning of the heat part is based on 

the ohmic

 resistance 

alteration

 in 

the 

t

h

e

rmi

stor 

as a result of the ambience

 temperature change. The smoke  sensitivity and the temperature class are 

factory preset. The fire detector is controlled by a microprocessor, operating on the basis of improved algorithm for 
self-compensation of the chamber contamination.
 

 

 The fire detector 

(fig.1)

 consists of 

printed circuit board, an optic chamber (pos.4), and 

a thermistor

 (pos.9). 

They are fixed in a plastic bo

dy

 (ïîç.5).

  

  

Both LED indicators (pos.3) allow range of visibility 360° and provide information for the status: 

-Duty mode

 – the LEDs are not lit;

-Fire condition

 – the LEDs produce continuous light

;

-Contaminated chamber

 — the LEDs flash briefly every 1s.

051-7

Reviews: