Operation
65
Main menu - Options - System - Ignition
The ignition type can be individual ignition or interval ignition. The ignition break
always equals the ignition duration. The longest possible ignition duration is 100
sec. Normally it should be between 15 and 20 sec. Upon reaching the ignition
threshold the ignition stops.
The ignition threshold specifies at which centigrade value the thermal battery
considers the flame to be burning. The flame temperature depends on the gas
composition. The settings are done accordingly. The manufacturer pre-sets the
optimum temperature for the ordered measuring range. In this example 3°C
differential temperature between cooling air and flue gas.
Main menu - Options - System - CSV export
Here you export the data as ASCII files. The values are TAB-separated. In one go,
all possible 25 curves are written in one CSV file. This file can be processed with
Excel.
Main menu - Options - System - Signal hold on/off
Here, the last measured values are issued as constant signal during the calibration.
This refers to all 4-20 mA signals. They are always switched on or off jointly.
Summary of Contents for CWD2000 EX
Page 1: ...April 2015 V1 04 Original operating instructions Combustion calorimeter CWD2000 EX ...
Page 6: ...Table of contents 6 ...
Page 9: ...Technical data 9 ...
Page 10: ......
Page 12: ...Table of contents 12 ...
Page 20: ...Table of contents 20 2 3 ...
Page 21: ...Safety devices 21 4 5 ...
Page 38: ...Table of contents 38 ...
Page 42: ...Table of contents 42 ...
Page 48: ...Table of contents 48 9 6 Menu structure ...
Page 81: ...Operation 81 ...
Page 82: ......
Page 86: ...Table of contents 86 ...
Page 90: ...Table of contents 90 ...
Page 98: ...Table of contents 98 ...
Page 100: ...Table of contents 100 ...