4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table 
below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the main is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 

mains.   

The AC input is connected 
to the UPS output. 

Plug  AC  input  power  cord 
to AC input correctly.   

The icon 

and the warning 

code 

  flashing on LCD display 

and alarm is sounding every 

second. 

EPO function is activated. 

Set  the  circuit  in  closed 

position  to  disable  EPO 
function. 

The icon 

and 

  flashing 

on LCD display and alarm is 
sounding every second. 

Line and neutral 
conductors of UPS input 
are reversed. 

Rotate mains power socket 
by  180°  and  then  connect 
to UPS system. 

The icon

  and 

flashing 

on LCD display and alarm is 

sounding every second. 

The external or internal 
battery is incorrectly 

connected. 

Check  if  all  batteries  are 
connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icons of 

  and 

 

are flashing on LCD display and 
alarm is sounding twice every 
second. 

UPS is overload   

Remove excess loads from 

UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 
fed directly by the 

electrical network via the 
Bypass. 

Remove excess loads from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove excess loads from 
UPS output first. Then shut 

down  the  UPS  and  restart 
it. 

Summary of Contents for Online UPS 1K

Page 1: ...Rack Tower Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 2 User Manual...

Page 2: ...view 3 2 2 Install the UPS 4 2 3 Setup the UPS 5 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 7 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 12 3 4 LCD disp...

Page 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...al package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table Model No Type Model No Type 1K Standar...

Page 6: ...ong run models 11 Input terminal 12 Output circuit breaker 2 2 Install the UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS plea...

Page 7: ...port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your...

Page 8: ...m 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring sof...

Page 9: ...the unit 2 5 Battery Kit Assembly option NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Ste...

Page 10: ...battery packs on one side of plastic shells and insert one more defect battery on the space Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit...

Page 11: ...ow chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of pl...

Page 12: ...e if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the...

Page 13: ...voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates that progr...

Page 14: ...D display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape RAC Rack display TOE Tower display B L Low Battery O L Overload N C Battery is not connected O C Overcha...

Page 15: ...127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage...

Page 16: ...isable Interface Setting ENA Advanced ECO mode enable DIS Advanced ECO mode disable 06 Bypass mode enable disable Interface Setting ENA Bypass mode enable DIS Bypass mode disable 07 Programmable outle...

Page 17: ...the following Acceptable input voltage range 110 300 alternating flashing acceptable input voltage range is from 110V to 300V 160 260 alternating flashing acceptable input voltage range is 160V to 26...

Page 18: ...y Corrective Optimizer When the input voltage is within setting range 3 Vo max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode When i...

Page 19: ...nder 03 x Battery voltage too high 27 x Bus unbalance 04 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 x High Inverter voltage 12 x Overload 43 3 8 Warning indicator W...

Page 20: ...hing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lig...

Page 21: ...ring and if connected devices are in short circuit status Fault code is shown as 01 02 03 04 11 12 13 and 41 on LCD display and alarm is continuously sounding A UPS internal fault has occurred There a...

Page 22: ...ealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperat...

Page 23: ...12V 9Ah Depending on application 12V 9Ah Depending on application 12V 9Ah Depending on application Numbers 2 3 4 6 Typical Recharge Time 4 hours recover to 90 capacity for standard model only Charging...

Reviews: