NOVA AND NOVA PRO
Measurements
46
Step 2
Connect test cable to the NOVA instrument and follow the connection
diagram shown in figure 5.44 to perform a voltage and frequency measurement.
Figure 5-394: Connection diagram
Step 3
Check the displayed warnings. The Voltage and Frequency test continually runs,
showing fluctuations as they occur, these results are shown on the display during
measurement.
Figure 5-405: Examples of voltage and frequency measurements
Displayed results:
U L-N ......
Voltage between phase and neutral conductors,
U L-PE .....
Voltage between phase and protective conductors,
U N-PE .....
Voltage between neutral and protective conductors.
When testing three-phase system the following results are displayed:
U 1-2 .......
Voltage between phases L1 and L2,
U 1-3 .......
Voltage between phases L1 and L3,
U 2-3 .......
Voltage between phases L2 and L3,