PART IV: MAINTENANCE
34
At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry
out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6
months.
ROUTINE MAINTENANCE
Check that the gas meter is not moving when the burner is off. In case it is rotating, look for possible leaks.
Check the cleaning condition of the vent. Clean the vent by using exclusively a dry brush. If needed, disassemble it from the
motor’s shaft and wash it by using non corrosive detergents. Prior to disassemble the vent, take the measurements in relation to
the motor's shaft, so as to reassemble it in the same position.
Check that all parts in contact with combustive air (air box, protection mesh and Archimedean screw) are clean and free from any
obstruction that might impede free afflux. Clean it with compressed air if available and/or a dry brush or cloths. Eventually wash it
with non corrosive detergents.
Check the blast tube; it must be substituted in case of obvious cracks or anomalous holes. Slight deformations that do not affect
combustion may be tolerated
Check the condition of the burner-boiler gasket. Eventually substitute it.
Check the fan’s motor: no specific maintenance is needed. In case of anomalous noises when running, check the condition of the
bearings and eventually substitute them or completely substitute the motor.
Clean and examine the gas filter cartridge and replace it if necesssary;
Remove and clean the combustion head;
Examine and clean the ignition electrodes, adjust and replace them if necessary;
Examine and clean the detection electrode/photoelement (according to the burner models), replace it if necessary, in case of
doubt, check the detection circuit, after the burner start-up;
Clean and grease leverages and rotating parts.
Attention:
Read carefully the “warnings” chapter at the beginnig of this manual
All operations on the burner must be carried out with the mains disconnected and the fuel manaul cutoff valves closed!
Any maintenance, cleaning or check intervals are a mere indication: the functionality of the burner - and its components -
depends, among other things, from capacity utilisation rate, environment, nature and quality of the fuels used
never loose the sealed screws! otherwise, the device warranty will be immediately invalidate!
ATTENTION: when servicing, if it was necessary to disassemble the gas train parts, remember to execute the gas
proving test, once the gas train is reassembled, according to the procedure imposed by the law in force.
At least every 2 months, or more frequently depending on the case, clean the burner installation room.
Avoid leaving installations, papers, nylon bags, etc., inside the room. They could be sucked by the burner and cause mal-
functioning.
Check that the room’s vents are free from obstructions.
PART IV: MAINTENANCE
Summary of Contents for RX1025.1
Page 41: ......
Page 42: ......
Page 43: ......
Page 45: ...User manual Siemens LMV 5x M12914CA Rev 0 03 2008...
Page 46: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 62: ...Annex1 Example for motor cable...
Page 63: ......
Page 64: ...Annex 2 Example for sensor cable...
Page 65: ......
Page 66: ......
Page 70: ......