Replacing the detection electrode
To replace the detection electrode, proceed as follows:
1
remove the combustion head according to the procedure on paragraph “Removing the combustion head”;
2
by means of an allen key, loose the fixing screws of the detection electrode
ER
and replace it;
3
replace the combustion head.
E
F
G
ATTENTION:
avoid
the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), otherwise the boi-
ler’s operation would be compromised. Check the electrodes position after any intervention on the combustion head.