C.I.B. UNIGAS
- M039241CB
5
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical Specifications
Heavy oil net calorific value (Hi): 9650 kcal/kg (average value).
*NOTE ON THE BURNER WORKING SERVICE: for safety reasons, one controlled shutdown must be performed after 24 hours
of intermittent operation.
WARNING:
the burners are supplied for 400V three phase supply; in case of three phase 230V supply, replace the thermal overload
relays. Maximum output is referred to a null backpressure in the furnace.
Type
PBY70
Model
H-. AB. S. *. A.
(1) (2) (3) (4) (5) (6)
(1) BURNER TYPE
PBY70
(2) FUEL
H - heavy oil , high viscosity
4000cSt (530°E) @ 50°C
(3) OPERATION
(
Available versions)
AB - Double stage
(4) BLAST TUBE
S - Standard L - Extended
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A - Standard
BURNER
PBY70
Output
min - max kW
290 - 1300
Fuel
Heavy oil
Oil viscosity
see “Burner model identification”
Heavy oil rate
min.
-
max. kg/h
26 - 116
Gas pressure
max. mbar
500
Gas pressure after gas governor
mbar
100
Compressed air pressure
bar
4 - 10
Oil train inlet pressure
bar
2 max
Power supply
400V 3N a.c. 50Hz
Total power consumption
kW
7.2
Pump-fan motor
kW
2.2
Pre-heater resistors
kW
4.5
Protection
IP40
Weight (approx)
kg
130
Operation
Double stage
Operating temperature
°C
(-10) / (+50)
Storage Temperature
°C
(-20) / (+60)
Working service*
Intermittent
PART I: INSTALLATION
Summary of Contents for PBY70
Page 7: ...C I B UNIGAS M039241CB 7 Overall dimensions mm boiler recommended drilling template ...
Page 16: ...C I B UNIGAS M039241CB 16 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0024 ...
Page 18: ...C I B UNIGAS M039241CB 18 Fig 9 Hydraulic diagram 3I2D 01 ...
Page 37: ...C I B UNIGAS M039241CB 37 ...
Page 42: ......
Page 43: ......