Heavy oil pumps
The pump provided with the burner must be installed according to the hydraulic diagram.
Cucchi FMG25 pumps
Capacity 1500l/h
kW
0.75
Speed 1400
Max Outlet Pressure 10bar
Max Inlet Pressure 5bar
Min Inlet Pressure -0.4bar
For further details see the manifacturer documentation.
Suntec TV Pressure governor
Pressure adjustment
Remove cap-nut 1 and the gasket 2, unscrew the lock nut 4. To increase pressure,
twist adjusting screw 3 clockwise.
To decrease the pressure, twist screw counterclockwise. Tight the lock nut 4, refit the
gasket 2 and the cap nut 1.
Key
1
Cap nut
2
Gasket
3
Adjusting screw
4
Lock nut
5
Gasket
Fig. 11