PART I: SPECIFICATIONS
6
Burner model identification
Burner8s are identified by burner type and model. Burner model identification is described as foll
Technical Specifications
Type
HTP2000
Model
MG. MD. S.
*.
Y. 8.
80.
ES.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(8)
1 BURNER TYPE
HTP2000
2 FUEL
G - Light oil
M - Natural gas
3 OPERATION (Available versions)
MD - Fully modulating
4 BLAST TUBE
S - Standard
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard
Y - Special
7 EQUIPMENT
1 = 2 gas gas proving system
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
80 = DN80 100 = DN100 125 = DN125
8 MICRO-PROCESSOR CONTROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
EK = with O
2
trim control, with VSD control
HTP2000
Output
min. - max. kW
2550 - 15300
Fuel
Natural gas - Light oil
Category
(see next paragraph)
Gas rate min.-max.
min.- max. (Stm
3
/h)
270 - 1619
Pressure
mbar
(see Note 2)
Light oil rate
min.-max. kg/h
215 - 1290
Вязкость
cSt @ 40 °C
2 - 7.4
Oil density
kg/m
3
840
Oil train inlet pressure
bar
2 max
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
37.5
Электродвигатель
вентилятора
kW
37
Protection
IP40
Operation
MD -
Fully modulating
Gas train 80
ØValves / Connection
3” / DN80
100
Ø /
4” / DN100
125
Ø /
5” / DN125
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service
Continuous
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
);
Note2:
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%
Summary of Contents for HTP2000
Page 13: ...PART I SPECIFICATIONS 13 Gas pressure in combustion head kW...
Page 35: ...PART III OPERATION 35 Pump flow rate Nozzle flow rate...
Page 45: ...PART IV MAINTENANCE 45...
Page 46: ...PART IV MAINTENANCE 46...
Page 47: ...PART IV MAINTENANCE 47...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......