PART II: INSTALLATION
18
Fig. 8 - pipe port (3) for connecting the pilot gas train to the valves group of the main gas train
The procedures of installation fo the gas valves are showed in the next paragraphs, according to the gas train used:
threaded gas trains with Siemens VGD20..
flanged gas trains with Siemens VGD40..
Siemens VGD20.. and VGD40.. gas valves - with SKP2.. (pressure governor)
Mounting
When mounting the VGD.. double gas valve, two flanges are required (as for VGD20.. model, the flanges are threaded); to prevent
cuttings from falling inside the valve, first fit the flanges to the piping and then clean the associated parts;
install the valve;
the direction of gas flow must be in accordance with the direction of the arrow on the valve body;
ensure that the bolts on the flanges are properly tightened;
ensure that the connections with all components are tight;
make certain that the O-rings and gaskets between the flanges and the double gas valve are fitted.
Connect the reference gas pipe (
TP
in figure; 8mm-external size pipe supplied loose), to the gas pressure nipples placed on the
gas pipe, downstream the gas valves: gas pressure must be measured at a distance that must be at least 5 times the pipe size.
Leave the blowhole free (
SA
in figure). Should the spring fitted not permit satisfactory regulation, ask one of our service centres for a
suitable replacement.
Caution: the SKP2 diaphragm D must be vertical (see Fig. 9).
WARNING: removing the four screws BS causes the device to be unserviceable!
connection to the gas supply
network
3
to the burner
SIEMENS VGD40..
3
gas proving system connection (optional)
Summary of Contents for HTP2000
Page 13: ...PART I SPECIFICATIONS 13 Gas pressure in combustion head kW...
Page 35: ...PART III OPERATION 35 Pump flow rate Nozzle flow rate...
Page 45: ...PART IV MAINTENANCE 45...
Page 46: ...PART IV MAINTENANCE 46...
Page 47: ...PART IV MAINTENANCE 47...
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......