C.I.B. UNIGAS
- M039203CC
15
Light oil pumps
Keys
1
inlet (suction) G1/4
2
return and internal by-pass plug G1/4
3
outlet to the nozzle G1/8
4
pressure gauge port G1/8
5
vacuum gauge port G1/8
6
pressure adjusting screw
Connecting the light oil flexible hoses
To connect the flexible light oil hoses to the pump, proceed as follows, according to the pump provided:
1
remove the closing nuts
A
and
R
on the inlet and return connections of the pump;
2
screw the rotating nut of the two flexible hoses on the pump
being careful to avoid exchanging the inlet and return lines
: see
the arrows marked on the pump that show the inlet and the return (see prevoius paragraph).
Electrical connections
To execute the electrical connections, proceed as follows:
1
remove the cover from the electrical board, unscrewing the fixing screws;
2
execute the electrical connections to the supply terminal board as shown in the following diagrams,
3
check the direction of the motor;
4
refit the panel cover
Pump Suntec AL65
Viscosity range
2 ÷ 12 (cSt) mm
2
/s
Oil temperature
0 ÷ 60 °C
Inlet pressure
2 bar
Minimum inlet pressure
- 0,45 barto avoid gasing
Maximum return pressure
2 bar
Rated speed
3600 rpm
Respect the basic safety rules. make sure of the connection to the earthing system. do not reverse the phase and
neutral connections. fit a differential thermal magnet switch adequate for connection to the mains.
ATTENTION: before executing the electrical connections, pay attention to turn the plant’s switch to OFF and be
sure that the burner’s main switch is in 0 position (OFF) too. Read carefully the chapter “WARNINGS”, and the
“Electrical connections” section.
WARNING: The burner is provided with a jumper between terminals 6 and 7; in the event of connecting the high/low
flame thermostat remove this jumper before connecting the thermostat.
IMPORTANT: while connecting electric supply wires to burner’s teminal block be sure that ground wire should be
longer than phase and neutral ones.
WARNING: if the cable that connects the thermostats and the LME.. control box should be longer than 3 meters,
insert a sectioning relay following the attached electrical wiring diagram.
R
A