PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical Specifications
(*) NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
Type
H630A
Model
MG. MD. SR.
*.
A.
1.
80.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
1 BURNER TYPE
H455A, H630A, H685A,
2 FUEL
MG
: Natural gas-Light oil,
LG
: LPGLight oil,
CG
: Off-gas - Light oil
3 OPERATION (Available versions)
PR - Progressive MD - Fully modulating
4 BLAST TUBE
SR = Standard blast tube + ABS polymer (silenced) air intake
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard, Y - SpecialeSpecial
7 EQUIPMENT
1 = 2 gas gas proving system
8 = 2 gas gas proving maximum gas pressure switch
8 GAS CONNECTION
50 = Rp2, 65 = DN65, 80 = DN80, 100 = DN100
BURNER TYPE
H455A
MG..
H630A
MG..
H685A
MG..
H455A
LG..
H630A
LG..
H685A
LG..
H455A
CG..
H630A
CG..
H685A
CG..
Output
min. - max. kW
750 - 4550 700 - 6300 740 - 6850 750 - 4550 700 - 6300 740 - 6850 750 - 4550 700 - 6300 740 - 6850
Fuel
MG - Natural gas-Light oil
LG - LPG
-
Light oil
CG:
Off-gas
-
Light oil
Category
(see next paragraph)
(see next paragraph)
(see next paragraph)
Gas rate- Natural gas
min.- max. (Stm
3
/h)
79 - 481 74 - 667 78 - 725
-
-
-
-
-
-
Gas pressure
mbar
(see Note 2)
(see Note 2)
(see Note 2)
Light oil rate
min.- max. (Stm
3
/h)
63 - 384 59 - 531 62 - 578 63 - 384 59 - 531 62 - 578 63 - 384 59 - 531 62 - 578
LPG rate
min.- max. (Stm
3
/h)
-
-
-
28 - 170 26 - 235 28 - 256
-
-
-
Off-gas rate
min.- max. (Stm
3
/h)
-
-
-
-
-
-
154 - 932 143 - 1291 152 - 1404
Oil viscosity
cSt @ 40°C
2 - 7,4
Oil density
kg/m
3
840
Light oil train inlet
bar max
2
Power supply triphase
220V/230V 3~ / 380V/400V 3N ~ 50Hz
Auxiliary Power supply
220V/230V 2~ / 220V/230V 1N ~ 50Hz
Total power
kW
9,
1
11,2
11,2
9,
1
11,2
11,2
9,
1
11,2
11,2
Electric motor
kW
7,5
9,2
9,2
7,5
9,2
9,2
7,5
9,2
9,2
Pump motor
kW
1,1
1,5
1,5
1,1
1,5
1,5
1,1
1,5
1,5
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
Valves size / Gas connection
50 / Rp 2
Gas train 65
Valves size / Gas connection
65 / DN65
Gas train 80
Valves size / Gas connection
80 / DN80
Gas train 100
Valves size / Gas connection
100 / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service (*)
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
); for L.P.G. (net calorific value H
i
= 93.5 MJ/Stm
3
)
Note2:
Maximum gas pressure = 500mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%