Bulletin 30-015.003 

 

Copyright © 2017 Unico Inc.  

 

Page 9 

Water Connections 

If you are installing the hot water coil, remove the side 
coil access panel. Slide the coil into the cabinet if not 
already  installed  at  the  factory  and  reinstall  the  door 
panel. After removing plugs in the inlet and outlet holes, 
caulk around connections to prevent leakage.  

IL00176a.cvx

TO BOILER

COIL

FROM PUMP/BOILER

VENT

DRAIN

COIL

BOILER \ WATER

HEATER

 

Figure 13 Water Piping Schematic 

 
Pump and pipe sizing should be based on proper flow 
rate. Refer to Bulletin 20-019 for water coil capacities 
based on flow rate. 

Sweat the water connections, then fill the system. Install 
a vent valve at the highest point and a drain valve at the 
lowest point of the water system (refer to Fig. 11). Fill 
and  bleed  the  air  from  the  system.  If  unit  is  in  an 
unconditioned space care must be taken to prevent the 
water  from  freezing.  Use  a  glycol-water  antifreeze 
solution  with  a  freezing  point  below  the  coldest 
temperature expected 

 

 

 

As an alternate to an anti-freeze solution, the water can 
be  continuously  circulated  to  prevent  freezing.  If  the 
coil  will  not  be  used  for  an  extended  period  of  time 
during  cold  temperatures,  drain  the  system  then  flush 
with a glycol solution. 

Wiring 

WARNING! 

DISCONNECT ELECTRICAL SUPPLY BE-
FORE WIRING UNIT TO PREVENT 
INJURY OR DEATH FROM ELECTRICAL 
SHOCK. 

 

All electrical wiring must comply with all local codes 
and  ordinances.  Make  electrical  connection  in 
accordance with the wiring diagram shown in Fig. 12. 
Refer  to  separate  control  box  manual  for  additional 
wiring instructions.  

The vertical unit uses the EC motor and SCB control as 
standard.  The  vertical  unit  is  sold  as  230V  or  115V 
power. The wiring schematic in this manual is for 230V. 
For 115 V wiring, refer to the control box manual. Use 
a separate 1ph, 60/50 Hz power supply with a 15 amp 
fuse  or  breaker  and  appropriate  wire  gauge  per  local 
code.  

1.

 

Connect the power supply to terminals L1 and L2/N 
of the terminal block. 

The low voltage transformer is factory wired for a 
primary voltage of 230V. If power supply is 208V, 
move  the  switch  on  the  control  board  to  the  208 
setting.  

2.

 

Connect the ground to the ground terminal. 

3.

 

Plug the motor cable to the motor. 

4.

 

Connect  the  anti-frost  wires  if  using  a  refrigerant 
coil.  

5.

 

Connect the thermostat wires. 

6.

 

Connect the condensing unit wires.

Summary of Contents for V2430

Page 1: ...VERTICAL AHU INSTALLATION MANUAL BULLETIN 30 015 003 ...

Page 2: ...ON 6 PIPING 7 SEQUENCE OF OPERATION 11 CHECKING AIRFLOW 11 CHARGING A COOLING SYSTEM 12 CHARGING A HEAT PUMP SYSTEM 14 Certified to UL Standard 1995 Conforms to CAN CSA Standard C22 2 NO 236 Unico products comply with the European regulations that guarantee product safety ...

Page 3: ...m includes the blower motor and a cooling coil For the heating and cooling system both coils are provided The cooling coil is a heat pump coil B Style or E Style All insulated Unico System Vertical air handlers feature closed cell insulation for improved sound attenuation There is no exposed insulation The Unico System is a complete indoor comfort system that includes an indoor fan coil unit and s...

Page 4: ...erant coil so it is very important to verify that the air temperature leaving the refrigerant coil is always greater than 32 F If not or if unsure install an averaging air temperature thermostat on the front of the hot water coil to automatically shut down the system should the air entering the hot water coil fall below 35 F The same must be done if bringing in fresh outside air that could be belo...

Page 5: ...e unit high enough in the secondary drain pan for the drain line to clear the side DUCT CONNECTION Supply Plenum The unit must have a plenum attached to the blower discharge The plenum can be most any type of duct provided it is the correct size and is insulated The EC motor is variable speed so no restrictor plate is required The supply duct attaches to the air handler with a supply adapter sold ...

Page 6: ...th acoustical insulation typically duct liner The minimum height of the plenum duct is shown in figure 5 Figure 5 Minimum duct return Although Unico only supplies a single return system the return system can be redesigned for multiple returns The return duct system is not high velocity Therefore the return system static pressure should not exceed 0 15 inches of water column Generally this means si...

Page 7: ...EVENT THE FORMATION OF OXIDES The refrigerant lines are copper flare connections The sizes are shown in Table 4 Refer to the condensing unit manufacturer s instruction for proper line sizing information based on distance from condenser Table 3 Liquid and Suction line size Model Size Liquid line Vapor line 2430 3036 3642 1 4 Flare 3 8 Flare 3 8 Flare 1 2 Flare 5 8 Flare 3 4 Flare Install a liquid l...

Page 8: ...nnections by charging the system with 150 psig of dry nitrogen and check for leaks at all connections Locate the bulb at the 2 4 8 and 10 o clock position on a horizontal straight section of the suction line Attach the bulb to the tubing with the two pieces of cork tape that are provided Figure 12 For satisfactory expansion valve control good thermal contact between the bulb and the suction line i...

Page 9: ...ulated to prevent freezing If the coil will not be used for an extended period of time during cold temperatures drain the system then flush with a glycol solution Wiring WARNING DISCONNECT ELECTRICAL SUPPLY BE FORE WIRING UNIT TO PREVENT INJURY OR DEATH FROM ELECTRICAL SHOCK All electrical wiring must comply with all local codes and ordinances Make electrical connection in accordance with the wiri...

Page 10: ...Bulletin 30 015 003 Copyright 2017 Unico Inc Page 10 Figure 14 Wiring Schematic 230V ...

Page 11: ...ndoor unit The heating system is now operating in stage one If the first stage does not satisfy the thermostat the second stage thermostat calls for more heat This closes the W2 contacts and energizes the sequencer for electric heat When the second stage thermostat is satisfied the W2 circuit is broken and the sequencer is de energized The electric heating system is now off When the first stage th...

Page 12: ... want it and cut or punch a small hole in the duct Make the hole the same size as the metal tube to prevent leakage Insert the metal tube one inch 25 mm so that the tip of the tube is flush to inside wall of the duct and perpendicular to the air stream as shown in Fig 13 Attach the metal tube to the manometer using a rubber hose usually supplied with the manometer Record the pressure Note If the t...

Page 13: ...be insulated or strapped to the suction line and both insulated The same problem can occur for long refrigerant lines in this case increase the size of the liquid line to reduce the pressure drop CAUTION TO MAINTAIN PROPER HEAT PUMP OPERATION DO NOT STRAP THE LIQUID AND SUCTION LINES TOGETHER FOR HEAT PUMP SYSTEMS Superheat Method Do not charge the system based on superheat Superheat measurements ...

Page 14: ...se it is overcharged if the system was charged during cooling Likewise the system may cycle on the anti frost control because of a low refrigerant charge if the system was charged during heating To compensate for this charge difference some outdoor unit manufacturers have a charge compensator device that stores charge while in heating mode Unfortunately there are no add on devices to accomplish th...

Page 15: ...pump section being used Table 5 R410A Saturation Pressure Temperature F psig C kPa gauge 0 48 4 18 330 2 51 1 17 347 4 53 8 16 363 6 56 6 15 380 8 59 4 14 398 10 62 4 13 416 12 65 4 12 434 14 68 6 11 453 16 71 8 10 473 18 75 1 9 493 20 78 5 8 513 22 82 1 7 534 24 85 7 6 556 26 89 4 5 578 28 93 2 4 601 30 97 2 3 624 32 101 0 2 648 34 105 0 1 673 36 110 0 0 698 38 114 0 1 723 40 119 0 2 750 42 123 0...

Reviews: