COMMISSIONING AND OPERATION
4.1 - POSITIONING OF THE
TURBULATORS
The TRIOPREX-N boilers are designed to be
used in an output range to improve the
seasonal efficiency and the possibility to be
adopted in all the heating installations.
The output must be adjusted at the
commissioning stage, according to the system
designer indications and, in any case, within
the operation range for each boiler model
shown on pages 6 to 10 , by the burner
technician, which will determine the fuel
throughput.
In any case
the turbulators will be placed,
inside the relevant smoke pipes, at a
distance, from the front tube plate, as
shown in fig. 36.
When using the boiler at minimum output the
smoke temperature will not be lower than
160 °C.
In contrary case, before get in touch with our
After Sale Service Dept, ascertain that the
turbulators are in all the smoke pipes.
The commissioning of the burner must be
performed under the responsibility of a
specialized and well trained burner technician,
authorised by the burner manufacturer.
In that occasion a commissioning report has
to be filled out.
4
fig. 36
TX N 65
TX N 85
TX N 110
TX N 150
TX N 185
TX N 225
TX N 300
TX N 380
TX N 500
TX N 630
TX N 730
TX N 840
TX N 1100
TX N 1320
TX N 1600
TX N 1900
100
200
100
100
100
200
400
400
200
200
200
200
1100
1500
1500
1800
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
A =
Detail 1:
Fit the brush handle extension
onto the turbulator remover
Withdraw the pin from turbulator.
Detail 2:
Fit the pin in the radial hole with a hammer.
Detail 3:
Screw the turbulator remover onto the
turbulator.
Detail 4:
Turn up to unblock the turbulator.
Detail 5:
Withdraw the turbulator
Detail 6:
Turn the remover counterclockwise to
release the turbulator
The procedure from detail 3 to 6 has to be repeated for all the turbulators.
Turbulators removal
fig. 37