29
Set language
TIME
Set current time:
1. Minute 2. Hour
GERMAN
PARAMETERS DISPAYED AT THE COMMISSIONING STAGE
Default
IV
Value range
Designation
INSTALLATION
YEAR
Set current date
MONTH
Set current date
DAY
Set current date
BUS ID
11111
Enter heating circuit number “1”:
00-15 Standard 01
BUS ID
22222
Enter heating circuit number “2”:
00-15 Standard 02
5K SENSOR
00 = 5 KOhm NTC sensor
01 = 1 kOhm PTCsensor, code no. required;
after input, there is a restart of the controller
RETURN
end of INSTALLATION
Start INSTALLATION, Set value, Save value and next value
Start INSTALLATION, Set value, Save value and next value
Acc. to version
GERMAN
GERMAN
(-20) (20)
CONTRAST
0
Sensor, weekday
DISPLAY SEL
- - - -
Exit level using
RETURN
Default
IV
Value range
Designation
HOT WATER
00, 01 (OFF / ON)
1X DHW
00 = OFF
10 °C - 70 °C
DHW-TEMP 1
60 °C
10 °C - 70 °C
DHW-TEMP 2
60 °C
Exit level using
RETURN
10 °C - 70 °C
DHW-TEMP 3
60 °C
OK - 70K
BOB-VALUE
0K
00, 01 (OFF / ON)
CIRCL-P-DHW
00 = OFF
00, 01 (OFF / ON)
ANTILEGION
00 = OFF
PARAMETERS PROGRAMMABLE BY THE USER