3.15 - PROGRAMMING THE OPERATING PARAMETERS
Bmm parameters
Cod
Simb
Description
unit
min.
max.
Default setting
803
Srv
Enabled Services
0
1
48
ChSet
CH#1: Set-point
°C
20
85
784
BC
Local BuS address
0
7
816
mI
modbus Address
1
127
817
mT
modbus Time-out
sec.
0
240
896
Tu
°fahrenheit
0
1
799
AC
Input 0/10V
0
2
376
DI1
Programmable Input #1
0
3
322
Po
Pump: Post-circulation
min.
1
30
341
PL
Pump: minimum Control
%
0
100
313
Pr
Pump: maximum Control
%
0
100
31
HL
CH#1: minimum Set-point
°C
20
85
39
HH
CH#1: maximum Set-point
°C
20
85
792
CHP
CH: max. modulation
%
0
100
619
IG
Ignition modulation
%
30
80
527
Pu
fan: Imp./Pass
0
3
486
fP
fan: reg. Prop.
0
50
487
fI
fan: reg. Int.
0
50
489
fpl
fan: PWm min.
%
5
15
337
fr
modulation Gradient
%
1,0
100,0
526
fu
fan: max Speed
Hz
50
120
319
fH
maximum modulation
%
1,0
100,0
346
fL
minimum modulation
%
1,0
100,0
314
Sb
modulation on Standby
%
0
100
620
IP
Postpurge: fan
%
0
100
617
IGL
Ignition: mod. min.
%
0
100
618
IGH
Ignition: mod. max.
%
0
100
353
HP
CH PID: Proportional
°K
0
50
354
HI
CH PID: Integrative
0
50
478
Hd
CH PID: Derivative
0
50
34
HY
Burner Hysteresis
°K
5,0
20,0
336
HS
Temperature Gradient
°C/min
0
30
483
rP
Gen: Temp. Max Differential
°C
0,0
50,0
380
Al1
Programmable Sensor #1
0
2
777
AfC
APS Control
0
2
805
LV
mains Voltage
V
100
240
2590
Burner output
kW
10
1000
( )
Values for propane
ATTENTION!
Function reserved for After Sale
Service Centres only.
ATTENTION!
These functions are explained
in chapter chapter 8 (Device
setting) of the Ufly P installation
and maintenance manual.