34
3.12.4 - NOVAIREX BOILER SYSTEM FOR HEATING AND FOR THE PRODUCTION OF
DOMESTIC HOT WATER WITH TANK IN TANK STORAGE TANK AND BACK-UP BOILER (oil-fired)
Mors. 6 p. VERDE
Mors. 9 p. GRIGIO
RMV
P2
S5
S4
A
B
AB
Pg
N
N
J4
P3 P2
ALIMENTAZIONE
CALDAIA DI
SOCCORSO
Esempio di collegamento elettrico
su caldaia di soccorso con pannello
strumenti cod.21057
E
E
L1
T2
N
S3
T1
B4
L1
N
IG
11
41
32
12
31
230V~ 50Hz
2
1
3
4
4-
4
24
22
21
C
2
G-
V
6-6
7-7
8-
8
9-9
10-10
Ts
7
6
9
5
8
10
B
A
11
12
Ib
(60°÷90°C)
(100°C)
Te 1
F1 (max 4 A)
N
Ph
R
F
F
SF
VE
IR
P3
S2
Micr
o por
ta
TA
S5
SF
S3
S2
S4
Morsett. 7 poli colore VERDE
Morsett. 9 poli colore GRIGIO
Key:
IR
: heating system
Pg
: back-up boiler loading pump
P2
: loading/recirculation pump
P3
: system pump
RMV
: mixing valve (55°C)
SF
: flue gas probe
In the following configuration when the wood-fired boiler runs
out of loaded wood, if the automatic function has been selected
on the control board and
TA
is in demand, clean contact J3 11-
12 on the wood-fired control board closes. In this way pump
Pg
is powered and the back-up boiler burner switches on.
The burner switches off either because
TA
requirement is met
(in this case pump
Pg
also stops), or because the temperature
set in the operating thermostat of the back-up boiler has been
reached (in this case pump
Pg
does not stop).
In the event of wood-fired boiler over-temperature, during back-
up boiler operation, when the temperature in
S4
reaches the
value of parameter P1, pump
P2
starts and some of the energy
in the boiler is discharged into the puffer.
If the temperature in
S4
should further increase until reaching
the temperature value set in parameter P2, both the burner of
the back-up boiler and pump
P4
switch off, the system pump
P3
switches on and an audible alarm will signal the overtem-
perature.
In case of a demand for DHW, clean contact J3 11-12 on the
wood-fired boiler's control board closes, the burner of the back-
up boiler switches on and pump Pg starts.
The request occurs when the temperature in
S3
reaches the
temperature set in P5 and ends when
S2
reaches the tempera-
ture set in P6; the burner switches off and pump
Pg
stops.
The counter-exchange between probe
S4
and probe
S2
is con-
trolled by the wood-fired boiler.
S2
: storage tank temperature sensor (low point)
S3
: storage tank temperature sensor (high point)
S4
: flow temperature sensor of the boiler
S5
: return temperature sensor of the boiler
VE
: expansion vessel
BACK-UP BOIL-
ER SUPPLY
Example of electrical connection
on back-up boiler with panel board
code 21057
STORAGE EX-
CHANGER
Door micros
witch