18
WARNING: The minimum temperature allowed for storing the unit is 5°C.
12.2
PRODUCT FICHE AND TECHNICAL PARAMETERS ACCORDING TO REGULATION (EU) No 811/2013
PRODUCT FICHE – HP_OWER for low-temperature application (Tout: 35°C)
Supplier’s name
UNICAL A.G. spa
Model
HP_OWER 250
HP_OWER 350
HP_OWER 500
Seasonal space heating energy efficiency class
A
++
A
++
A
++
Rated heat output
under average climate conditions
18 kW
23 kW
35 kW
under colder climate conditions
17 kW
22 kW
33 kW
under warmer climate conditions
19 kW
23 kW
38 kW
Seasonal space heating energy
efficiency
under average climate conditions
150 %
152 %
150 %
under colder climate conditions
113 %
104 %
107 %
under warmer climate conditions
193 %
177 %
180 %
Annual energy consumption
under average climate conditions
9984 kWh
12357 kWh
19182 kWh
under colder climate conditions
14400 kWh
19952 kWh
29309 kWh
under warmer climate conditions
5266 kWh
6752 kWh
11162 kWh
Annual energy consumption
in terms of final energy
under average climate conditions
25459 kWh
31501 kWh
48916 kWh
under colder climate conditions
36960 kWh
51315 kWh
75334 kWh
under warmer climate conditions
13369 kWh
17165 kWh
28370 kWh
Sound power level, indoors L
WA
-
-
-
Sound power level, outdoors L
WA
70 dB(A)
74 dB(A)
77 dB(A)
Precautions for installation and maintenance
Read precautions for installation and maintenance at
specific chapters on user’s and installation’s manual.
PRODUCT FICHE – HP_OWER for medium-temperature application (Tout: 55° C)
Supplier’s name
UNICAL A.G. spa
Model
HP_OWER 250
HP_OWER 350
HP_OWER 500
Seasonal space heating energy efficiency class
A
+
A
+
A
+
Rated heat output
under average climate conditions
13 kW
23 kW
26 kW
under colder climate conditions
12 kW
22 kW
24 kW
under warmer climate conditions
14 kW
22 kW
27 kW
Seasonal space heating energy
efficiency
under average climate conditions
100 %
100 %
100 %
under colder climate conditions
81 %
83 %
74 %
under warmer climate conditions
130 %
113 %
110 %
Annual energy consumption
under average climate conditions
10662 kWh
18817 kWh
20948 kWh
under colder climate conditions
14082 kWh
24867 kWh
30795 kWh
under warmer climate conditions
5746 kWh
9999 kWh
12677 kWh
Annual energy consumption
in terms of final energy
under average climate conditions
27271 kWh
48434 kWh
53947 kWh
under colder climate conditions
36506 kWh
64425 kWh
80112 kWh
under warmer climate conditions
14696 kWh
25661 kWh
32558 kWh
Sound power level, indoors L
WA
-
-
-
Sound power level, outdoors L
WA
70 dB(A)
74 dB(A)
77 dB(A)
Precautions for installation and maintenance
Read precautions for installation and maintenance at