13
(2)
The management of the relaunching circulator requires the optional “GI” module code 00264034
6.6.3
PM Module phase protection
The PM module detects the correct sequence of the 3-phases (L1, L2, and L3) power supply. The 3-phases power supply must be
connected respecting the correct sequence of the phases so as to ensure the right direction of rotation at the compressor start-up
and during operation. When the PM module acts for lack of phase, the controller will receive a signal to interrupt it from the
power supply.
6.6.4
Plant management optional module terminal block CODE 00264034
Where the plant management kit (optional) is present, a third controller is located inside the electric panel, which acts as I/O
resource expansion module. With this controller, it is therefore possible to increase the number of logics handled by the main
controller; in particular these logics are used to manage the plant system and are reported below. The functions described below
can be activated by the on-board unit controller that is located on the unit’s front panel.
For the configuration of the functionalities, please check the control manual supplied with the unit.
DO1E
DO3E
DO5E
DO4E
ST5E
ST6E
DO2E
DO1EN
DO1EN
DO1E
DO3E
DO5E
DO4E
ST5E
ST6E
DO2E
ST7E
STE
ST7E
ST7E
ID3E
ID3E
ID3E
ID3E
DO2EN
DO3EN
DO4EN
DO5EN
ST5E
ST6E
DO2EN
DO3EN
DO4EN
DO5EN
ST5E
ST6E
ID2E
ID2E
ID2E
ID2E
ST8E
ST8E
ST78E
ST8E
AO2E
AO2E
AO2E
AO2E
AO1E
AO1E
AO1E
AO1E
TERMINAL
TYPE
CONNECTION
ID2E
Digital input
(1)
Ambient thermostat
ID3E
Digital input
(1)
Double setpoint
DO1E(Phase)
DO1E N(Neutral)
Under-voltage output 230V ac,
50Hz, 5A resistive, 1A inductive
Plant auxiliary heating element
(3)
Secondary (relaunching) circulator
DO2E(Phase)
DO2E N(Neutral)
Under-voltage output 230V ac,
50Hz, 5A resistive, 1A inductive
Domestic hot water auxiliary electric heater
(3)
Boiler’s activation
DO3E(Phase)
DO3E N(Neutral)
Under-voltage output 230V ac,
50Hz, 5A resistive, 1A inductive
Alarm warning
(3)
Lockout warning
DO6E(Phase)
DO6EN(Neutral)
Under-voltage output 230V ac,
50Hz, 5A resistive, 1A inductive
Double setpoint valve
(3)
Domestic hot water valve
DO7E(Phase)
DO7E N(Neutral)
Under-voltage output 230V ac,
50Hz, 5A resistive, 1A inductive
Plant season warning
(3)
Defrosting warning
(1)
Enablement from maintainer level
(3)
Otherwise