27
3.6 -
OUTER COMPENSATOR
On how to adjust or to program the outer
compensator, please refer to the instruction
manual supplied with the outer compensator.
In the following table we list the factory set
parameters, which are "not changeable" and
the parameters which are adjustable by the
user according to his needs.
Default
IV
Value range
Designation
INSTALLATION
0000 - 9999
CODE-NO
ENTRY
0000 - 9999
CODE-NO (Adjustment)
0000
(00), 01 - 15
BUS ID
11111
01
Exit level using
(00), 01 - 15
BUS ID
2
2
2
2
2
02
00,01 (OFF/ON)
AF SUPPLY
01 = ON
00, 01 (OFF / ON)
TIME MASTER
00 = OFF
30 °C - 110 °C
T-HS MAX
80 °C
PARAMETERS PROGRAMMABLE BY A TECHNICIAN AND PROTECTED BY AN ACCESS CODE
10 °C - 80 °C
MIN T-HS
60 °C
10 °C - 85 °C
WARM-UP-T
50 °C
5K - 20K
HYSTERESIS
5 gradi
00 min - 30 min
HYST TIME
10 min
00 min - 30 min
DELAY ST
10 min
2K - 20K
HYST BURNER 2
2K
0h - 250h
SEQ CHANGE (*)
0h (*)
00 - 08
RELAY FUNC 1
00
30 °C - 90 °C
RELAY-TEMP 1
30 °C
2K - 10K
HYST RELAY 1
5K
00 - 03
RELAY FUNC 2
00
00 - 01 (OFF / ON)
SCREED
00 = OFF
See explanation!
SCREED PROGR
RETURN
Default
IV
Value range
Designation
HOT WATER
00 - 01 (OFF / ON)
CP LOCK
01 = ON
00 , 01, 02, 03
PARALLEL
00
00 °C - 50 °C
HS-T DHW
20 °C
5K - 30K
HYST DHW
5K
00 min - 30 min
DHW FOLLOWUP
00 min
00, 01 (OFF / ON)
THERM INPUT
00 = OFF
00, 01 (OFF / ON)
CHARGE THROUGH
00 = OFF
Exit level using
RETURN
00, 01, 02
MIN-DELIMI
00
* The switching time of the parameter SEQ CHANGE (Sequence change) can be adjusted up to 250 h only if the controller is used for controlling
two boilers equipped with a single-stage burner each.
If the controller is used for controlling a boiler with a two-stage burner, the parameter SEQ CHANGE must be left at “0 h”.
It must be left also at “0 h” if the controller is used for controlling two boilers, of which one, for instance, has a better efficiency and, the second
one, is used only when the first one is out of order or is not capable to supply, alone, the total heat necessary for the heating system.