Installation info
2.2.3 - ASSEMBLING THE BOILER
Before connecting the boiler to the D.H.W.
and heating system pipes, carefully clean
the pipes to remove all traces of metal
resulting from processing and welding
operations as well as any oil and grease
which could damage the boiler or
jeopardize its operation.
Unical
refuses all liability for injury to persons
and animals or damage to property resulting
from non-observance of the above.To install
the boiler:
- Fix with tape the paper template to the
wall
- make two Ø 12 holes in the wall and
insert the hooks;
- position the junction points for the
connection of the gas supply pipe, cold
water supply pipe, D.H.W. outlet, CH flow
and return in the positions shown by the
template.
- fit the boiler onto the support hooks;
- connect the boiler to the gas pipe,
domestic cold and hot water pipes, CH
flow and return pipes.
- connect to electrical supply.
NOTE:
NOTE:
NOTE:
NOTE:
NOTE:
----- Do not use solvents which could
Do not use solvents which could
Do not use solvents which could
Do not use solvents which could
Do not use solvents which could
damage the components.
damage the components.
damage the components.
damage the components.
damage the components.
2.2.4 - VENTILATION
The boiler must be installed in a suitable room
according to the rules in force and particu-
larly:
NATURAL DRAUGHT OPEN FLUE BOI-
LERS
(TYPE B11bs and VMC INSTALLATIONS)
The boilers
DUA PLUS TN,
are open flue
boilers and are foreseen for chimney
connection: the air for combustion is taken
directly from the room in which the boiler is
installed.
The room can have both a direct ventilation
(i.e. with ventilation openings facing out-
wards) or an indirect ventilation (i.e. with ven-
tilation openings facing an adjacent room)
provided that the following requirements are
complied with:
Direct ventilation:
-
The room has to have a ventilation open-
ing of, at least,
6 cm² /kW of installed input (see input
table on par. 2.7) and, in no case, lower
than 100 cm² and made directly onto an
external wall.
-
The opening has to be as close as possi-
ble to the floor.
-
It should not be possible to close it and it
should be protected with a grate not re-
ducing its usefull ventilation section.
-
A correct ventilation can be optained also
through the addition of more openings,
provided the addition of the different sec-
tions is not less than that really needed.
-
In case it is not possible to make a venti-
lation opening close to the floor, it will be
necessary to increase its usefull section
of at least 50%.
-
If an open fire is present in the same room
it needs an indipendent air supply, other-
wise the installation of a type B appliance
is not permitted.
-
If in the room there are other devices
which need air for their operation (e.g. a
wall exhauster) the section of the venti-
lation opening has to be the properly si-
zed.
Indirect ventilation
In case it is not possible to make a room
ventilation opening on an external wall, it is
possible to have an indirect ventilation,
sucting the air from an adjacent room,
making an
opening in the lowest part of a door.
This solution is possible only if:
-
The adjacent room is not a bed room
-
The adjacent room is not a common part
of the building and is not a room with fire
danger (e.g. a fuel deposit, a garage, etc..)
FORCED DRAUGHT ROOM SEALED BOI-
LER
(TYPE C12 - C32 - C42 - C52 - C62 - C82)
The
DUA PLUS TFS
are forced draught,
room seal-ed boilers; so they do not need
particular ventilation openings for the
combustion air, in the room in which they
are installed.
FORCED DRAUGHT, OPEN FLUE
BOILER
(TYPE B22)
If the
DUA PLUS TFS
are installed in a room
ac-cording to the chimney configuration on
type
B22,
the same ventilation requirements
established in paragraphs
Direct
ventilation
and
Indirect ventilation
apply.
rectangular section, the internal section
must be 10% larger than the section of
the connection duct to the draught
diverter.
-
starting from the draught diverter, the duct
must have a vertical section with a length
more than twice the diameter, before get-
ting into the chimney.
2.2.5 - FLUE GAS DISCHARGE
SYSTEM
NATURAL DRAUGHT OPEN FLUE BOI-
LERS
Connection to the chimney
A good chimney is very important for the
correct functioning of the boiler; it must
therefore conform with the following
requirements:
-
it must be made from waterproof material
and be resistant at the temperature of
the flue gas and relative condensate;
-
it must have sufficient mechanical
strength and low thermal conductivity;
-
it must be perfectly sealed to prevent
cool-ing due to parasite air inlets;
-
it must be as vertical as possible and the
end section must have a chimney cap
which guarantees efficient and constant
evacuation of the combustion products;
-
the chimney must have a diameter not
smaller than that of the boiler’s draught
diverter; for chimneys with a square or