19
Installation info
2.3.2 - POSITIONING OF THE JUMPERS (their purpose is to implement some functions necessary for the operation
fig. 11
JUMPERS ON THE DISPLAY PCB
JP4
: GAS TYPE SELECTION
Naturl gas
: Jumper on NAT (standard supply position)
Liquefied Petroleum Gas
: move jumper to LPG position
The standard supply position correspond to the gas type shown on all
the labels within the boiler
JP3
: EXTRNAL TEMPERATURE COMPENSATION FOR OUTER SENSOR
Boiler with outer temperature sensor: jumper on
J
Boiler without outer temperature sensor: jumper on
OFF
JP2
: SELECTION OF PUMP OPERATION MODE
If pump has to work continuously: jumper on
1
If pump has to stop after an overrun of 5 min since the stop of the heating
demande: jumper on pos.
2
(standard supply position)
JP1
: CHRONOSTAT FUNCTION
(do not change posion of the jumper)
This function is not yet available.
Jumper on
(Standard supply position: for a good working keep the jumper in
this position).
T°C
0
1
2
3
4
5
6
7
8
9
0
32755
31137
29607
28161
26795
25502
24278
23121
22025
20987
10
20003
19072
18189
17351
16557
15803
15088
14410
13765
13153
20
12571
12019
11493
10994
10519
10067
9636
9227
8837
8466
30
8112
7775
7454
7147
6855
6577
6311
6057
5815
5584
40
5363
5152
4951
4758
4574
4398
4230
4069
3915
3768
50
3627
3491
3362
3238
3119
3006
2897
2792
2692
2596
60
2504
2415
2330
2249
2171
2096
2023
1954
1888
1824
70
1762
1703
1646
1592
1539
1488
1440
1393
1348
1304
80
1263
1222
1183
1146
1110
1075
1042
1010
979
949
90
920
892
865
839
814
790
766
744
722
701
Relation between the temperature (°C) and the resistance (Ohm) of the heatin temp. sensor SR and the D.H.W. temp. sensor
SR. Example: At 25 °C the nominal resistance is 10067 Ohm - At 90 °C the resistance is 920 Ohm.
TABLE OF THE RESISTANCE VALUES ACCORDING TO THE TEMPERATURE OF THE HEATING SENSOR (SR) AND
D.H.W. TEMPERATURE SENSOR (SS)
NAT
GPL
OFF
JP4
JP3
J
JP2
JP1
1
2
1
2
POSITIONING OF THE JUMPER