18
Instructions for the installer
fig. 16
The thermostats bulbs can be identified by labels stickers
fixed on the respective capillary. Therefore, during any mainte-
nance, pay attention that the labels will not be removed.
A) Place the bulb of the working thermostat (Te), of the Max
thermostat, (Tmax), of the Min. Thermostat (Tsc) and of
the thermometer in the central bulb holder
B) Place the bulb of the safety thermostat (Ts) in the R.H. side
bulb holder
C) Fix the bracket (pos. 1), supporting the fan socket to
casing L.H. side panel, using the 3 screws, supplied with
the product, and tighten the screw (pos. 2) on the smoke
chamber.
Fit on the bracket the fan socket (pos. 3).D)
Con-
nect the fan plug to the socket (pos. 3)
E) Make the electrical connections of the supply line, the
pump(s) and other possible devices according to the wiring
diagrams shown in chapters 3.12 and 3.13.
Close the panel board.
Pay attention that the cables do not come in contact with
the smoke chamber. During operation, this reaches high
temperatures
.
TERMOSTATO
DI ESERCIZIO (Te)
TERMOMETRO
MOLLA
DI CONTATTO
TERMOSTATO
DI MINIMA (Tsc)
MOLLA DI
FISSAGGIO
TERMOSTATO
DI MASSIMA (Tmax)
TERMOSTATO
DI SICUREZZA (Ts)
MOLLA DI
FISSAGGIO
3
2 1
The solid fuel boilers must be installed with all the securi-
ty devices foreseen by the laws in force.
For this purpose, AIREX boilers are equipped with a built-
in safety heat exchanger.
A) Connect the safety discharge valve (pos. 1) and insert its
temperature sensor into the bulb holder (pos.2)
The safety discharge valve may be mounted either on the
right or on the left.
It is recommended to convey the discharge of the safety
heat exchanger.
Remember that for the solid fuel boiler, due to the thermal
inertia of the fuel, the installation of the termal discharge
valve is required.
SCARICO
1
2
ALIMENTAZIONE
fig. 17
WORKING THERMOSTAT (Te)
THERMOMETER
MINIMUM THERMOSTAT (Tsc)
FIXING CLIP
CONTACT SPRING
HIGH LIMIT THERMOSTAT (Tmax)
FIXING CLIP
SAFETY THERMOSTAT (Ts)
MAINS
DRAIN