Owner’s Manual and Installation Instructions

Trouble Shooting & Repair

Knowledge of electrical applications is required for trouble shooting. Contact a certified electrician
if you are unsure of your ability to service the equipment. Improper servicing will void the ozonator
warranty. If any condition persists, call UltraPure at 877 281 7603 for further technical assistance.

PUMP IS OVERLY NOISY OR LOOSES PRIME WHILE RUNNING:

Note:

A small amount of noise can be expected since air is being drawn into the pump and works
its way through the filter and pipes. Problems are solved by using one or more of the fol-
lowing alternatives; moving the injection point “up stream“ from the pump; and/or reduc-
ing the airflow; and/or increasing the water flow.

Plug the 3/8”tubing (unit end) with the pump running and check for a suction side plumbing leak.
Install the suction side injection point in the plumbing upstream before the pump.
Reduce air draw by either turning the Dial Flowmeter (on equipped models) clockwise or adding
more Threaded Rod into the tubing.

AIR “BLOW BACK” THROUGH THE SKIMMER LINE(S):

Note:

An air build up in the filter will cause this. When the pump shuts off, air expands and seeks
“the path of least resistance” to escape. This path is usually through the skimmer line. This
problem is solved by completely removing air from the filter while the pump is running, or by
stopping air from backing up through the suction (skimmer) line(s).

Extend or install the internal air bleed line inside the filter. By ensuring this internal air bleed line is
as close to the top of the filter as possible, air readily escapes as the pump runs.

Where the External Safety Air Bleed Kit (ESABK) is installed, ensure that it is actually releasing the
air being introduced into the filter. The pressure gauge port or the manual air bleed port will work
well on most filters. In some instances, the air bleed(s) inside the filter must be drilled out larger. To
check that our ESABK is letting air out of the filter shut off the pump; disconnect the black tubing at
the filter; hold your thumb over the tubing end (to close it off); start the pump and see that air (and
some water) is coming out of the compression fitting at the tee. Once you have a good air bleed,
shut off the pump and reconnect the tubing.

PUMP LOSES PRIME OR HAS TROUBLE “CATCHING PRIME”

AFTER IT HAS BEEN SHUT OFF:

Note:

This problem is limited to retrofit installations. It is caused by either a suction side air leak;
a filter (multi-port) air leak; or air in the filter partially blowing back past the pump. In any
case, the pump has an “air lock”.

Install a 2 lb. or 1 lb. water line check valve just below (on the suction side) of the pump.

Repair or replace the multi port valve gasket.

To help diagnose a plumbing air leak problem, plug the “unit end” of the black tubing to

see if the problem ceases.

Where the pump has a “lift” more that 3 to 4 feet, order a stronger (than 1

1

/

2

lb.) spring

loaded check valve from UltraPure Water Quality Inc. A 3 lb. or 6 lb. spring loaded check
valve may be required.

UltraPureManual12pg34072.indd   9

UltraPureManual12pg34072.indd   9

24.03.16   15:09

24.03.16   15:09

Summary of Contents for Automatic Water Cleaner UPP15

Page 1: ...ner s Manual and Installation Instructions FOR INGROUND AND ABOVE GROUND MODELS WATER QUALITY INC Part 3704700 UltraPureManual12pg34072 indd 1 UltraPureManual12pg34072 indd 1 24 03 16 15 09 24 03 16 15 09 ...

Page 2: ...ntee 2 Specifications 3 Installation Location Mounting the UltraPure Water Cleaner Electrical 4 Plumbing Builder Standpipe Install Retrofit Install 5 Installation Instructions 6 External Safety Air Bleed Kit 7 8 Trouble Shooting Repair 9 Terms and Conditions of Warranty UltraPureManual12pg34072 indd 2 UltraPureManual12pg34072 indd 2 24 03 16 15 09 24 03 16 15 09 ...

Page 3: ...r death The UltraPure Automatic Water Cleaner must be installed in an outdoor location or indoors in a forced air ventilated room Warning Short term inhalation of high concentrations of ozone and long term inhalation of low concentrations of ozone can cause serious harmful physiological effects DO NOT inhale ozone gas produced by this device Ozone is considered toxic above certain concentrations a...

Page 4: ... free soft to the touch water Easy to manage pool water chemistry and balancing Compatibility with any chlorine source algaecides and minerals The lowest chemical use of any system While Ozone is not a disinfectant to kill algae and bacteria and does not provide a measurable residual it is the best Oxidizer for bather waste removal An UltraPure UV Ozone generator pays for itself while delivering a...

Page 5: ...nnect the UltraPure Automatic Water Cleaner to the pool timing clock so that the UltraPure operates simultaneously with the pool pump or plug your 120V unit into a grounded receptacle Above ground units come complete with a 120V Piggy back cord The circuit must be protected by a ground fault circuit interrupter G F C I installed in accordance to electrical code Operating your UltraPure Automatic W...

Page 6: ...e for pressure testing the plumbing When you are ready to install the UltraPure Automatic Water Cleaner cut the cap from the 3 4 standpipe and glue on our 3 4 FSL x 1 4 FPT reducing coupling Apply Teflon tape and screw in the 1 4 MPT x 3 8 straight compression fitting into the reducing coupling The 1 1 2 lb compression check valve is not required and should NOT be used with the method Connect the ...

Page 7: ...h the metal grippers PRESSURE SIDE VENTURI INSTRUCTIONS kit sold separately See instructions included with the Pool Venturi Conversion Kit Part 1008079 For some applications a pressure side installation may be desired This kit is available for purchase separately ABOVE GROUND INSTALLATION The above ground installation is very similar to the above retrofit installation All above ground units come c...

Page 8: ...pump or on newer filters which will not evacuate the air See parts package included with your UltraPure Automatic Water Cleaner OPERATION To achieve optimal performance from the UltraPure Automatic Water Cleaner the pool must be as clean as possible to start with Back wash or clean the filters before starting the UltraPure Automatic Water Cleaner Test the pool water and adjust as stated in the cha...

Page 9: ... the internal air bleed line inside the filter By ensuring this internal air bleed line is as close to the top of the filter as possible air readily escapes as the pump runs Where the External Safety Air Bleed Kit ESABK is installed ensure that it is actually releasing the air being introduced into the filter The pressure gauge port or the manual air bleed port will work well on most filters In so...

Page 10: ...t lamp s in your UltraPure Automatic Water Cleaner may have difficulty starting The quartz ozone pro ducing lamp have mercury vapor inside and the cold temperature causes the mercury to condense and make the lamp s more difficult to start This occurs in all Ultra Violet Ozone generators Note A small amount of condensation may become apparent inside the Dial Flowmeter This is normal and does not in...

Page 11: ...e areas c If no ASD is in the area the manufactured goods in need of service should be shipped with RGA to the address on the RGA form freight prepaid Any returned item deemed faulty due to manufacturer defect will be repaired or replaced and shipped back to the customer at no charge to the customer d The owner of the goods may be responsible for all expenses if the field serviced or returned item...