1. ULLS10RF PRODUCT OVERVIEW

All UltraFire Photoelectric type smoke alarms are approved to the most 

recent and rigorous European Smoke Alarm Standard. The unique X-Profile 

Photoelectric sensing chamber is particularly sensitive to slow smouldering fires 

typically originating in living rooms, bedrooms and hallways whilst being highly 

resistant to nuisance alarms.

Product Features 

• 

Radio interlinkable to other UltraFire 10 year smoke and heat alarms. By 

connecting up to 15 alarms, they will be connected by radio link so that 

when one alarm sounds all connected alarms will sound.

• 

Two sealed in long life batteries.

• 

Approved to EN14604:2005, Smoke alarm devices.

• 

Unique X-Profile detection chamber with insect screen.

• 

Bespoke software maximizes detection ability, false alarm rejection and 

Alarm Silence operation.

• 

Power automatically switched on as a alarm is installed onto its mounting 

plate and automatically switched off when alarm is removed.

• 

Red LED on the alarm and the green one on the side of the mounting 

pattress will flash approximately every minute confirming unit is receiving 

power and ready to detect and transmit fire conditions. (Quiescent Mode)

• 

Low Battery Warning - End of alarm life, alarm gives one beep every 

minute.

• 

Low Battery Warning Silence - Low battery warnings often start at night. 

Silence the audible warning for ten hours by pressing the test button, thus 

avoiding removing the alarm from its mounting plate. The alarm can then 

be replaced when convenient the following day.

• 

Extra Large Test Button for ease of use, tests sensitivity, circuitry, battery 

and alarm sounder.

• 

Loud 85 Decibel Piezo Electric Alarm - Automatically resets when 

hazardous condition has passed and chamber is clear.

• 

Alarm Silence - Silence your smoke alarm by momentarily pressing the 

test button. Ideal in non-emergency situations where nuisance alarms 

may have been created, for example, by steam. The red light flashes 

every 12 seconds to remind you that the smoke alarm has been silenced 

and will automatically reset to quiescent mode in 10 minutes.

• 

Approved for use in Leisure Accommodation Vehicles.

2. CHOICE AND LOCATION OF ALARMS

Photoelectric Smoke Alarms are best for sensing smouldering fires and 

therefore best suited for rooms containing furniture, bedding and clothes 

such as escape routes, lounges, bedrooms and other living rooms. They are 

recommended by BS 5839 pt6 for living accommodation where most fires 

originate in electrical equipment and smouldering material such as furniture, 

clothing, curtains and carpets.

NOTE: Heat Alarms are most suitable for kitchens, boiler rooms, workshops 

and garages where dust, dirt and moisture would contribute to nuisance alarms. 

Heat alarms should not be used on walls or in escape routes and should 

always be interlinked to smoke alarms. Do not install heat alarms in sleeping 

areas; for example, bedrooms, nurseries, playrooms or areas where the elderly 

and disabled may spend long periods of time.

For minimum protection, install at least one smoke alarm on each level of your 

home. They should be installed in hallways, corridors and all escape routes 

from the building and within 3 meters of all bedroom doors. All alarms should 

be interconnected.

Recommended siting of smoke and heat alarms in:

SINGLE STOREY HOME WITH ONE 

SLEEPING AREA

SINGLE STOREY HOME WITH TWO 

SLEEPING AREAS

MULTIPLE STOREY HOME WITH 

MULTIPLE SLEEPING AREAS

6. 

Do not install less than 300mm from walls and light fittings when mounted 

on the ceiling where heat and dead air may delay smoke reaching the alarm.

7. 

Do not install in insect infested areas.

8. 

Do not install in areas subjected to heavy concentrations of cigarette smoke 

that will cause nuisance alarms and the alarm to become contaminated.

9. 

Do not install smoke alarms in kitchens, boiler rooms and garages where 

fumes and dust may cause nuisance alarms.

10.  Do not install on poorly insulated walls and ceilings where cold air boundary 

layers could prevent smoke reaching the alarm.

11.  Do not install near objects that could prevent smoke and heat reaching the 

alarm.

12.  Do not install within 1500mm of fluorescent light fitting that could trigger 

nuisance alarms.

13.  Do not paint the alarm.

The location of the alarms must be in accordance with applicable building 

regulations, in particular Part B. Further help and guidance can also be found in 

BS5839 part 6.

 

4. FURTHER DETAIL ON ALARM LOCATION

1. 

At least one smoke alarm should be installed in the escape route on all 

floors of the building.

2. 

The detection element of smoke alarms should be between 25mm and 

600mm below the ceiling, or in the case of heat alarms between 25mm and 

150mm

3. 

Smoke alarms should be at least 300mm from any wall or light fitting.

4. 

If ceiling mounting is impractical smoke alarms may be installed on walls 

provided that the area is no longer or wider than 10 metres and the total 

area does not exceed 50m2 and that: 

a. 

The detection element is between 150mm and 300mm below the 

ceiling.

b. 

The bottom of the detection element is above openings such as vents, 

doors and opening windows

c. 

Ensure they are not mounted close to or above heaters or air-

conditioning vents.

5. 

Where smoke alarms are located in a hallway, corridor or landing, the alarm 

should be no further than three metres from any bedroom door to assist 

audibility behind closed doors.

6. 

No point on the ceiling in any room, hallway or corridor should be further 

than 7.5 metres from any smoke alarm.

7. 

To give the earliest warning of a developing fire, smoke alarms should be 

installed in all the rooms of your home and interlinked. (other than those in 

point 2 of Choice and Location of Alarms above).

6. INSTALLATION PROCEDURE

Pairing the Radio System

Refer to the separate “Instructions for Pairing Radio Linked Alarms” in the 

previous section.

1.  When the pairing of the complete system has been completed, test all alarms 

to make sure they all link to one another. If they do not, re-pair the alarms 

according to the instruction sheet packed with the alarms.

2.  Now take the complete alarm to the rooms of their location and test the system 

again to make sure that they still operate correctly in their new location

3.  Now separate the alarms from their radio pattresses by depressing the 

security tag shown below and twisting the alarm anticlockwise 

4.  Fix them to your final chosen location by referring to sections 2, 3, and 4 

above and re-assemble the alarm to the pattress as shown below

5.  You need to ensure surfaces do not contain hazardous materials eg asbestos. 

The screw fittings supplied are suitable for use on wood, plaster and 

plasterboard but on other surfaces such as concrete where adhesive material 

or adhesive pads may be better. For certain applications, the installer may 

need to source their own fixings.

5. INTERLINK INSTRUCTIONS

1. 

Preparing the alarms:

a. 

Plug the alarm into the RF base and switch the RF base on.

b. 

Fit the alarm onto the RF base and twist to lock them; the alarm will 

beep twice to indicate it is powered on. 

c. 

Repeat these steps for all alarms you wish to interlink. 

2. 

Interlinking the alarms: 

a. 

Press the test button on one alarm, wait 3 seconds, and then press 

the test button on a second alarm; the alarms will sound a test 

sequence. 

b. 

The LED indicators on both RF bases will flash green and red for a 

while before one will flash only green, the other will continue with red 

and green until it beeps and then will also flash only green. 

c. 

If adding further alarms to the system keep the alarm that beeped in 

the last step, move the other to the side, take a new unlinked alarm, 

then repeat steps a. and b. until all alarms have been connected.

3. 

If any RF base flashes red only during the interlinking steps or if you need to 

remove an alarm from your system for any reason:

a. 

Push the security tag in the side of the alarm, then twist to separate 

the alarm and the RF base. 

b. 

Press the black button inside the RF base, next to the on/off switch; 

the LED on the RF base should flash red four times.

c. 

You can now attempt to interlink the alarm again, or turn the RF base 

off and unplug the alarm to remove it from the system.

RECOMMENDED POSITION OF 

ALARMS IN A ROOM, CORRIDOR OR 

ESCAPE ROUTE:

3. AVOID THE FOLLOWING LOCATIONS

The life of this alarm can be significantly reduced by adverse environments, 

incorrect location and a failure to regularly clean and maintain it according to the 

following instructions. Incorrect location and a lack of reasonable care may also 

cause it to malfunction and will invalidate the warranty. 

NOTE: Do not store alarms in temperatures below 5°C and above 30°C; this 

may cause beeping and nuisance alarms when first installed. These will clear 

after a short time when the alarm has become acclimatised. Extended periods 

under these conditions will reduce the life of the alarms and invalidate the 

warranty.

1. 

Do not locate near fans or extractors. These can pull smoke and heat away 

from the alarms.

2. 

Do not install in or near high humidity areas such as showers, bathrooms 

or kitchens where humidity levels exceed 85% or the room temperature 

exceeds 40° or falls below 0°C. These may cause nuisance alarms and 

damage the alarm.

3. 

Do not install alarms in the peak of an “A’ frame. This may delay smoke and 

heat reaching them due to the presence of dead air.

4. 

Do not install less than 300mm from walls and light fittings when mounted 

on the ceiling where heat and dead air may delay smoke reaching the alarm.

5. 

Do not install in insect infested areas.