The Ultra Aire Dehumidifier plugs into a common grounded 115 VAC outlet. Locate the dehumidifier in an
area where the cord’s length (9') easily reaches a 115 VAC electrical outlet with a minimum of 15 Amp circuit
capacity. If used in an area that may become wet, a GFCI protected circuit is recommended. Consult local
electrical codes for further information.
Ultra Aire offers a variety of control devices for use with the Ultra Aire Dehumidifier. The control is to be located
remotely from the dehumidifier and placed in the space to be conditioned. A low voltage (24 Volt) control MUST be
used with the Ultra Aire Dehumidifier and MUST be connected with low voltage (18-22 gauge) thermostat wire.
ELECTRICAL REQUIREMENTS
CAUTION!
CAUTION!
DO NOT ALLOW THE 24V TERMINAL TO CONTACT THE COM/DMPR TERMINALS ON THE
ULTRA AIRE DEHUMIDIFIER OR DAMAGE TO THE TRANSFORMER WILL RESULT.
Electrical Precautions
• Do not install the control where it may not accurately sense the relative humidity such as near HVAC
supply registers, near exterior doors, on an outside wall, near a window, or near a water source.
• The screw terminals on the Ultra Aire Dehumidifier and the control are labeled to prevent confusion.
• Be sure to consult the electrical schematic in the CONTROLS Section (page 12) of this manual or inside
the access panel of the Ultra Aire Dehumidifier before making control connections.
WARNING!
WARNING!
THE REMOTE CONTROLS OF THE ULTRA AIRE DEHUMIDIFIER ARE POWERED BY A LOW VOLTAGE
CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE CIRCUIT.
CAUTION!
CAUTION!
SOME OF THE SCREW TERMINALS ON THE ULTRA AIRE DEHUMIDIFIER MAY NOT BE USED
WITH CERTAIN CONTROLS AND SHOULD BE LEFT UNCONNECTED.
Ultra Aire 98H Wiring Diagram
Ultra Aire 120H Wiring Diagram