Model 200DX
::
Ultimateair.com
::
Athens, Ohio 45701 :: 740.594.2277
0-10 VDC Input Signal Control System
Your RecoupAerator can be programmed into a “smart house” control, so it
may be controlled remotely or using any 0-10 VDC control signal.
To set up a 0-10 VDC input signal control system,
disconnect all power to
the unit
.
1.
Set jumpers JMP1 to the EU position, and J3 to the 0-10V INPUT
position on the three-motor controller as shown in the drawing
below to enable the 0-10 VDC control input.
2.
If a Wall Dial Control is attached to the unit, remove it. You do not
need a Wall Controller when operating the unit with a 0-10VDC input
control signal.
3.
Locate the two screw terminals labeled “0-10V CMD INPUT”, as
shown above, and connect the signal control wires to these posts as
indicated.