background image

With all high efficiency boilers, care must be taken to minimize

condensation.  Therefore, 

cold  standby  is  not

recommended

 and may be used only with a piping, bypass

as shown on Figure 12. This requires a change in control

wiring. Please contact factory prior to making that change.
When  cold  standby  is 

not

  utilized,  the  homeowner  might

possibly object to the burner starting when space heat is not

required. To avoid this, an optional outside thermostat may

be  used  to  shut  down  the  system  totally  when  outside

temperature is above a specific limit set by the homeowner.

When outside thermostat is not used, Jumper T-T Terminals

on relay.

L8151 CONTROL SETTINGS

Use the following setting for the first adjustment:

17

High Limit Set Point .............. 180°F

Low Limit Set Point ............... 160°F

Differential ............................... 20°F

These settings may be altered based on the heating system

response. During very cold weather if the heating system does

not provide quite enough heat, the high limit control setting

may be raised to a maximum of 200°F. If more domestic hot

water is required, the low limit control setting may also be

raised to a maximum of 180°F. Whenever adjusting either the

high or low limit the high limit control setting must be set at

least 20°F above the low limit. The differential control setting

is typically 20°F but may be adjusted to vary the time it takes

the burner to respond to a call for domestic hot water.

Oil Burner and Controls Start-Up and Adjustment

INDOOR DIRECT EXHAUST BOILERS

Instruction manual enclosed in burner carton must

be followed in regard to start-up and adjustment

1. A Beckett model AFG post-purge oil burner is normally

supplied with boilers to be fired at 2.00 gph or less. It is

equipped with an F3 flame retention head, the size most

commonly  used. 

It  is  possible  the  head  must  be

changed to match the nozzle firing rate required, 

and

it  is  recommended  the  installer  carry  a  complete

assortment of Beckett flame retention heads. When head

ratings overlap, a smaller head with air shutter fairly well

open will generally provide better combustion than a larger

head with air shutter near closed.
SEE  HEAD  SIZE  SELECTION  CHART  ON  PAGE  16.

SUGGESTED NOZZLES, HEADS, AND PRELIMINARY

SETTINGS  FOR  VARIOUS  FIRING  RATES  ARE

SHOWN ON PAGE 40.

2. At firing rates above 2.00 gph, a 

special 

Beckett

 

model

CF375 burner 

must

 be used and is supplied if specified

by purchaser.

3. Post-purge oil burners are supplied with pump pressure

set at 140 psi. Nozzle output will be approximately 18%

greater than that at 100 psi.

4.

The burner is not supplied with a nozzle. 

The correct

nozzle is the smallest which will do the job properly. Long

continuous runs with minimum starts and stops conserve

the most energy. The nozzle which provides the highest

C02 with the least smoke for a particular application is

always recommended.

5.

WARNING:

 Too low a firing rate can cause excessive

condensation within the boiler and flue resulting in severe

rust and corrosion. A piping by-pass is recommended to

minimize this problem. See Figure 12.

6. If Beckett AFG burner is to be fired at less than 1.00 gph,

it is possible that a low firing rate baffle will be required.

For firing rates not specified on page 40, see chart below

on which an “x” indicates that a baffle is necessary. See

also instruction sheet with baffle in burner carton.

HEAD

FIRING RATE, GPH

LOW FIRE BAFFLE

.50

X

.65

X

.75

.75

X

.85

X

.90

1.00

.85

X

.90

X

1.00

F0

F3

F6

7. Using three acorn nuts, studs and washers from hardware

package, fasten burner to mounting plate. Do not disturb

chamber when inserting firing head.

8. Mount L8151 control on boiler jacket above and to the

right of burner using sheet metal screws in holes located

in jacket. Wiring harness is provided. When well is used

at  the  rear  of  a  larger  boiler,  it  might  be  necessary  to

relocate the control with longer wiring not provided.

9. If boiler has a tankless coil, insert well for the L8151 remote

bulb in coil plate. Run capillary tube through sight glass

opening in jacket.

10. If a tankless coil is not used, install 3/4" well and bulb with

a bushing either in the 1 1/2” supply opening opposite the

one used to feed radiation, or in a reducing tee in the 1 1/2”

supply opening that feeds radiation.

11. Mount overfire pressure switch at upper right of burner

on screws already in jacket. Connect by 1/4" copper tube

to brass tee at upper left of burner.

Burner will shut down if overfire pressure reaches .17"

H2O due to a plugged flue or high wind. If high wind

causes nuisance shutdowns, mount switch on an angle

bracket with diaphragm horizontal. Shutdown will then

occur at .25" H2O.

Summary of Contents for PF Series

Page 1: ......

Page 2: ......

Page 3: ...60 74 64 87 5 88 23 4 6 14 Maximum 1 35 159 138 83 3 83 91 4 6 14 Minimum 75 93 81 87 5 88 23 5 6 17 Maximum 1 70 199 173 83 9 84 63 5 6 17 Minimum 1 05 130 113 87 6 88 24 7 7 24 Maximum 2 35 276 240...

Page 4: ......

Page 5: ...Minimum 95 112 97 82 8 88 25 Maximum 2 10 239 208 79 6 85 20 6 One 37 7 Minimum 1 10 129 112 82 4 88 22 Maximum 2 50 294 256 7 Two 44 3 Minimum 1 25 147 128 82 7 88 15 Maximum 2 75 309 268 8 One 44 3...

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ...with 130 square inches of FREE opening Metal grilles have about 60 FREE area To find the louvered area needed multiply the FREE area required by 1 7 130 x 1 7 221 0 sq in louvered area In this exampl...

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ...chart below on which an x indicates that a baffle is necessary See also instruction sheet with baffle in burner carton 6 Using three acorn nuts studs and washers from hardware package fasten burner to...

Page 18: ......

Page 19: ...SETTINGS FOR VARIOUS FIRING RATES ARE SHOWN ON PAGE 40 2 At firing rates above 2 00 gph a special Beckett model CF375 burner must be used and is supplied if specified by purchaser 3 Post purge oil bur...

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...rate is changed combustion must be checked with instruments With chamber fully warmed up find highest C02 level at which zero smoke can be maintained Then add extra air until C02 falls off about 1 Fin...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ...DQNOHVV RLO LW 6LQJOH 3DVV QFOXGHV DQG 7DQNOHVV RLO 7Z R 3DVV 7DQNOHVV RLO LW 7Z R 3DVV QFOXGHV DQG 7DQNOHVV RLO DVNHW ODQN RLO 3ODWH 66 6WXG UHT G 1 XW H 6HUUDWHG 6 6 6LJKW ODVV VVHPEO RLO 6HFWLRQ 6W...

Page 38: ......

Page 39: ......

Page 40: ...1260006 Temperature Pressure Gauge 6 1060002 3 4 x 1 4 Bushing 7 146 22 011 3 4 ASME Relief Valve 8 146 07 202 3 4 x 4 1 2 Nipple 9 146 07 012 1 1 4 x 10 Nipple Except Models 7TT 8T 9 9 146 07 206 1 1...

Page 41: ......

Page 42: ...1 00 80 A F 6 1 1 8 No 10 1 AFG 1 70 1 50 80 A F12 1 1 8 No 10 3 AFG DPFO 7 1 00 90 80 B F 3 1 1 8 No 10 0 AFG 1 60 1 35 80 B F12 1 1 8 No 10 1 AFG 2 35 2 00 60 B SV1 3 No 10 2 5 CF375 DPFO 9 1 35 1 2...

Page 43: ......

Page 44: ...14683825 Rev 2 May 2003...

Reviews: