background image

Fresh Air for Combustion - Chimney Vented Boilers

8

WARNING

Be sure to provide enough fresh air for combustion.

Enough air ensures proper combustion and 

assures that

no hazard will develop due to the lack of oxygen.

You  must  provide  for  enough  fresh  air  to  assure  proper

combustion. The fire in the boiler uses oxygen. It must have a

continuous  supply. The  air  in  a  house  contains  only  enough

oxygen to supply the burner for a short time. Outside air must

enter the house to replace that used by the burner. Study following

examples 1 and 2 to determine your fresh air requirements.

EXAMPLE 1: Boiler Located in Unconfined Space

If your boiler is in an open area (unpartitioned basement) in a

conventional house, the air that leaks through the cracks around

doors and windows will usually be adequate to provide air for

combustion. The doors should not fit tightly. Do not caulk the

cracks around the windows.
An unconfined space is defined as a space whose volume is not

less than 50 cubic feet per 1,000 Btu per hour of the total input

rating of all appliances installed in the space.

EXAMPLE 2: Boiler Located in Confined Space

A.

All Air from Inside the Building:

 The confined space shall

be  provided  with  two  permanent  openings  communicating

directly with an additional room(s) of sufficient volume so that

the combined volume of all spaces meets the criteria for an

unconfined space. The total input of all combustion equipment

installed in the combined space shall be considered in making

this determination. Each opening shall have a minimum free

area of one square inch per 1,000 Btu per hour of the total

input rating of all combustion equipment in the confined space,

but not less than 100 square inches. One opening shall be

within 12 inches of the top and one within 12 inches of the

bottom of the enclosure. See Figure 5.

Example:

 Your boiler is rated at 100,000 Btu per hour. The

water  heater  is  rated  at  30,000  Btu  per  hour. The  total  is

130,000 Btu per hour. You need two grilles, each with 130

square inches of FREE opening. Metal grilles have about 60%

FREE area. To find the louvered area needed, multiply the

FREE area required by 1.7 (130 x 1.7 = 221.0 sq. in. louvered

area). In this example two grilles, each having an 8" x 30"

(240 sq. in.) louvered area would be used. Fig. 5 shows the

grille locations.

B.

All Air from Outdoors:

 The confined space shall be provided

with  two  permanent  openings,  one  commencing  within  12

inches of the top and one commencing within 12 inches of the

bottom of the enclosure. The openings shall communicate

directly, or by ducts, with the outdoors or spaces (crawl or

attic) that freely communicate with the outdoors.
1. When  directly  communicating  with  the  outdoors,  each

opening shall have a minimum free area of one square

inch  per  4,000  Btu  per  hour  of  total  input  rating  of  all

equipment in the enclosure.

2. When communicating with the outdoors through vertical

ducts, each opening shall have a minimum free area of

one square inch per 4,000 Btu per hour of total input rating

of all equipment in the enclosure.

NOTE

If you use a fireplace or a kitchen or bathroom exhaust

fan, you should install an outside air intake. These devices

will rob the boiler and water heater of combustion air.

3. When communicating with the outdoors through horizontal

ducts, each opening shall have a minimum free area of

one square inch per 2,000 Btu per hour of total input rating

of all equipment in the enclosure.

4. When ducts are used, they shall be of the same cross-

sectional area as the free area of the openings to which

they connect. The minimum dimension of rectangular air

ducts shall be not less than three inches.

¼" Mesh

Screen Btuh

Wood

Louvers Btuh

Metal

Louvers Btuh

3½"

x

12"  

144,000

36,000

108,000

8"

x

8"  

256,000

64,000

192,000

8"

x

12"  

384,000

96,000

288,000

8"

x

16"  

512,000

128,000

384,000

Fresh Air

Duct Size

FIG. 5 - AIR OPENINGS FOR CLOSET OR

UTILITY ROOM INSTALLATIONS

Fresh Air Duct Capacities for Ducts Supplying Fresh Air to

boiler in tightly constructed houses.  British Thermal Units

per hour input (Btuh)*.

FIG. 6 - FRESH AIR DUCT CAPACITIES

* Based on opening covered by 1/4” mesh screen, wood louvers, or metal louvers

FIG. 7

FRESH AIR DUCT FOR TIGHTLY SEALED HOUSE

Summary of Contents for PF Series

Page 1: ......

Page 2: ......

Page 3: ...60 74 64 87 5 88 23 4 6 14 Maximum 1 35 159 138 83 3 83 91 4 6 14 Minimum 75 93 81 87 5 88 23 5 6 17 Maximum 1 70 199 173 83 9 84 63 5 6 17 Minimum 1 05 130 113 87 6 88 24 7 7 24 Maximum 2 35 276 240...

Page 4: ......

Page 5: ...Minimum 95 112 97 82 8 88 25 Maximum 2 10 239 208 79 6 85 20 6 One 37 7 Minimum 1 10 129 112 82 4 88 22 Maximum 2 50 294 256 7 Two 44 3 Minimum 1 25 147 128 82 7 88 15 Maximum 2 75 309 268 8 One 44 3...

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ...with 130 square inches of FREE opening Metal grilles have about 60 FREE area To find the louvered area needed multiply the FREE area required by 1 7 130 x 1 7 221 0 sq in louvered area In this exampl...

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ...chart below on which an x indicates that a baffle is necessary See also instruction sheet with baffle in burner carton 6 Using three acorn nuts studs and washers from hardware package fasten burner to...

Page 18: ......

Page 19: ...SETTINGS FOR VARIOUS FIRING RATES ARE SHOWN ON PAGE 40 2 At firing rates above 2 00 gph a special Beckett model CF375 burner must be used and is supplied if specified by purchaser 3 Post purge oil bur...

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...rate is changed combustion must be checked with instruments With chamber fully warmed up find highest C02 level at which zero smoke can be maintained Then add extra air until C02 falls off about 1 Fin...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ...DQNOHVV RLO LW 6LQJOH 3DVV QFOXGHV DQG 7DQNOHVV RLO 7Z R 3DVV 7DQNOHVV RLO LW 7Z R 3DVV QFOXGHV DQG 7DQNOHVV RLO DVNHW ODQN RLO 3ODWH 66 6WXG UHT G 1 XW H 6HUUDWHG 6 6 6LJKW ODVV VVHPEO RLO 6HFWLRQ 6W...

Page 38: ......

Page 39: ......

Page 40: ...1260006 Temperature Pressure Gauge 6 1060002 3 4 x 1 4 Bushing 7 146 22 011 3 4 ASME Relief Valve 8 146 07 202 3 4 x 4 1 2 Nipple 9 146 07 012 1 1 4 x 10 Nipple Except Models 7TT 8T 9 9 146 07 206 1 1...

Page 41: ......

Page 42: ...1 00 80 A F 6 1 1 8 No 10 1 AFG 1 70 1 50 80 A F12 1 1 8 No 10 3 AFG DPFO 7 1 00 90 80 B F 3 1 1 8 No 10 0 AFG 1 60 1 35 80 B F12 1 1 8 No 10 1 AFG 2 35 2 00 60 B SV1 3 No 10 2 5 CF375 DPFO 9 1 35 1 2...

Page 43: ......

Page 44: ...14683825 Rev 2 May 2003...

Reviews: