OMMISSIONING AND OPERATION
13
5.2
Operation
Trigger the opening of the connected locking unit via the third-party system con-
nected to connections 3 and 8. Connection 3 serves as ground.
Switching input: High: 5-24 VDC
Low: 0 VDC
The high level must be present for at least 25 ms to trigger the switching opera-
tion.
5.3
Resetting
Disconnect the device from the power supply.
5.4
Resetting the configuration (factory reset)
If you want to reset all the settings, proceed as follows:
Use a screwdriver or a similar tool to turn the rotary switch (6) so that the arrow-
head points to Position 9. Briefly press the button (7) to delete all the saved lock-
ing units and parameters.
5.5
Firmware updates
The update tool "Clex FW Prog" is available to
update the firmware. Contact your respective dealer or Integration partner.
5.6
Signaling
LED
Meaning
Blue
slow flashing
Device scans for paired locking unit
Blue
flashing
BLE activity with connected locking unit
Blue
constant lighting up
Paired locking unit is connected
Blue
rapid flashing
Device tries to wake up a locking unit in the "wake on
radio" mode (WOR)
Yellow
Button input
Red/green
flashing alternatingly
Connected with the locking unit in service mode
Green constant light-
ing + blue flashing
Service mode
After reset: One-time
all colors consecutive-
ly
Device has completed the initialization
5.7
Malfunctions during operation/error signaling