4
U N I T E D E L E C T R I C C O N T R O L S
1 0 0 B - 0 2
100 Series
1
0
0
S
e
ri
e
s
1 0 0 B - 0 2
U N I T E D E L E C T R I C C O N T R O L S
5
10 0 S e r i e s
1.5” sanitary welded 316L stainless steel diaphragm and pressure connection. Mates with Tri-Clamp® fitting systems
565
5 to 30
0,3 to 2,1
1 to 5
0,07 to 0,3
1000
68,9
1500
103,4
566
10 to 100
0,7 to 6,9
1 to 12
0,07 to 0,8
1000
68,9
1500
103.4
567
15 to 300
1,0 to 20,7
3 to 22
0,21 to 1,5
1000
68,9
1500
103,4
Buna N diaphragm and O-Ring with 1/4” NPT (female) nickel-plated brass pressure connection; Option M540 Viton® diaphragm and O-Ring
available for models 701-705
701
1.5 to 30
0,1 to 2
1 to 2
0,07 to 0,14
500
34,5
600
41,4
702
3 to 100
0,2 to 6,9
1 to 4
0,07 to 0,28
500
34,5
600
41,4
703
9 to 300
0,6 to 20,7
1 to 5
0,07 to 0,34
500
34,5
600
41,4
704
15 to 500
1,0 to 34,5
2 to 8
0,14 to 0,55
1500
103,4
2500
172,4
705
30 to 1000
2,1 to 68,9
3 to 20
0,21 to 1,38
1500
103,4
2500
172,4
706
100 to 1700
6,9 to 117,2
10 to 30
0,07 to 2,07
2000
137,9
2500
172,4
Viton® diaphragm and O-Ring with 1/4” NPT (female) 303 stainless steel pressure connection (includes adjustable deadband switch)
15623
20 to 200
1,4 to 13,8
12 to 26
0,8 to 1,8
500
34,5
1000
68,9
316L stainless steel diaphragm (optional Hastelloy® C, Monel® or Tantalum); Viton® GLT O-Ring (optional Kalrez®, Silicone, Ethylene Propylene, or
Aflas®); 316 stainless steel 1/2” NPT (female) pressure connection (optional Hastelloy® B or C, or Monel®), large 0.72” orifice for clean-out purposes.
Models 188 and 189 have a 316L stainless steel 1/2” NPT (female) pressure connection
183
1 to 20
0,07 to 1,4
0.3 to 2.5
0,021 to 0,2
500
34,5
1000
68,9
184
2 to 50
0,14 to 3,4
0.3 to 3
0,021 to 0,2
500
34,5
1000
68,9
185
4 to 100
0,3 to 6,9
0.5 to 6
0,03 to 0,4
500
34,5
1000
68,9
186
8 to 200
0,6 to 13,8
1 to 11
0,07 to 0,8
500
34,5
1000
68,9
188
50 to 1000
3,4 to 68,9
25 to 125
1,7 to 8,6
2000
137,9
7000
482,6
189
250 to 3500
17,2 to 241,3
50 to 300
3,4 to 20,7
4000
275,8 7000
482,6
Welded 316 stainless steel diaphragm with 1/2” NPT (female) pressure connection, large 0.72” orifice for clean-out purposes
Lower 75% range span Top 25% range span
psi
bar
psi
bar
psi
bar
psi
bar
psi
bar
190
5 to 30
0,3 to 2,1
1 to 3
0,07 to 0,2 6 max
0,4
1500
103,4
2500
172,4
191
10 to 100
0,7 to 6,9
1 to 8
0,07 to 0,6 15 max
1,0
1500
103,4
2500
172,4
192
15 to 300
1,0 to 20,7
3 to 18
0,2 to 1,2
25 max
1,7
1500
103,4
2500
172,4
193
20 to 500
1,4 to 34,5
4 to 30
0,3 to 2,1
45 max
3,1
1500
103,4
2500
172,4
194
80 to 1700 5,5 to 117,2
5 to 120 0,3 to 8,3
150 max
10,3
2000
137,9
2500
172,4
Welded 316 stainless steel diaphragm with 1/2” NPT (female) pressure connection, 0.06” orifice to dampen pulsations
490
5 to 30
0,3 to 2,1
1 to 3
0,07 to 0,2 6 max
0,4
1500
103,4
2500
172,4
491
10 to 100
0,7 to 6,9
1 to 8
0,07 to 0,6 15 max
1,0
1500
103,4
2500
172,4
492
15 to 300
1,0 to 20,7
3 to 18
0,2 to 1,2
25 max
1,7
1500
103,4
2500
172,4
493
20 to 500
1,4 to 34,5
4 to 30
0,3 to 2,1
45 max
3,1
1500
103,4
2500
172,4
494
80 to 1700 5,5 to 117,2
5 to 120 0,3 to 8,3
150 max
10,3
2000
137,9
2500
172,4
Model
Adjustable Set Point Range
Deadband
Over Range
Proof
Low end of range on fall;
Pressure*
Pressure**
High end of range on rise
psi
bar
psi
bar
psi
bar
psi
bar
Type H100
Hastelloy
®
is a registered trademark of Haynes International, Inc.
Monel
® is a registered trademark of the INCO family of companies.
Viton® and Kalrez®
are registered trademarks of Dupont Dow Elastomers.
Aflas®
is a registered trademark of Asahi Glass, Inc.
* Over Range Pressure:
The maximum pressure that may be applied continuously without causing damage and maintaining set point repeatability.
** Proof Pressure:
The maximum pressure to which a pressure sensor may be occasionally subjected, which causes no permanent damage. The unit may require calibration (e.g., start-up, testing).
Deadband Note:
Models 190-194, 490-494 are expressed as the lower 75% and top 25% of the range span because of the operating characteristics of the diaphragm sensor and switch.