UE 100 Serie Installation And Maintenance Instructions Manual Download Page 16

RECOMMENDED PRACTICES AND WARNINGS

United  Electric  Controls  Company  recommends  careful  consideration  of  the 
following  factors  when  specifying  and  installing  UE  pressure  and  temperature 
units.  Before  installing  a  unit,  the  Installation  and  Maintenance  instructions 
provided with unit must be read and understood. 
•  To avoid damaging unit, proof pressure and maximum temperature limits 
 

stated in literature and on nameplates must never be exceeded, even by 

 

surges in the system. Operation of the unit up to maximum temperature 

 

is acceptable on a limited basis (i.e., start-up, testing) but continuous 

 

operation must be restricted to the designated adjustable range. Excessive 

 

cycling at maximum temperature limits could reduce sensor life.

•  A back-up unit is necessary for applications where damage to a primary 
 

unit could endanger life, limb or property. A high or low limit switch is 

 

necessary for applications where a dangerous runaway condition 

 

could result.

•  The adjustable range must be selected so that incorrect, inadvertent 
 

or malicious setting at any range point cannot result in an unsafe 

 

system condition.  

•  Install unit where shock, vibration and ambient temperature fluctuations 
 

will not damage unit or affect operation. Orient unit so that moisture does 

 

not enter the enclosure via the electrical connection. When appropriate, 

 

this entry point should be sealed to prevent moisture entry.

•  Unit must not be altered or modified after shipment. Consult UE if 
 

modification is necessary.  

•  Monitor operation to observe warning signs of possible damage to unit, 
 

such as drift in set point or faulty display.  Check unit immediately.

•  Preventative maintenance and periodic testing is necessary for critical 
 

applications where damage could endanger property or  personnel.

•  For all applications, a factory set unit should be tested before use.
•  Electrical ratings stated in literature and on nameplate must not be 
 

exceeded. Overload on a switch can cause damage, even on the first 

 

cycle.  Wire unit according to local and national electrical codes, 

 

using wire size recommended in installation sheet.

•  Do not mount unit in ambient temp. exceeding published limits.

LIMITED WARRANTY

Seller  warrants  that  the  product  hereby  purchased  is,  upon  delivery,  free  from 
defects in material and workmanship and that any such product which is found 
to be defective in such workmanship or material will be repaired or replaced by 
Seller  (Ex-works,  Factory,  Watertown,  Massachusetts.  INCOTERMS);  provided, 
however,  that  this  warranty  applies  only  to  equipment  found  to  be  so  defective 
within a period of 24 months from the date of manufacture by the Seller.  Seller 
shall not be obligated under this warranty for alleged defects which examination 
discloses  are  due  to  tampering,  misuse,  neglect,  improper  storage,  and  in 
any  case  where  products  are  disassembled  by  anyone  other  than  authorized 
Seller’s  representatives.  EXCEPT  FOR  THE  LIMITED  WARRANTY  OF  REPAIR 
AND  REPLACEMENT  STATED  ABOVE,  SELLER  DISCLAIMS  ALL  WARRANTIES 
WHATSOEVER  WITH  RESPECT  TO  THE  PRODUCT,  INCLUDING  ALL  IMPLIED 
WARRANTIES  OF  MERCHANTABILITY  OR  FITNESS  FOR  ANY  PARTICULAR 
PURPOSE. 

LIMITATION OF SELLER’S LIABILITY

SELLER’S  LIABILITY  TO  BUYER  FOR  ANY  LOSS  OR  CLAIM,  INCLUDING 
LIABILITY  INCURRED  IN  CONNECTION  WITH  (I)  BREACH  OF  ANY  WARRANTY 
WHATSOEVER,  EXPRESSED  OR  IMPLIED,  (II)  A  BREACH  OF  CONTRACT,  (III) 
A  NEGLIGENT  ACT  OR  ACTS  (OR  NEGLIGENT  FAILURE  TO  ACT)  COMMITTED 
BY  SELLER,  OR  (IV)  AN  ACT  FOR  WHICH  STRICT  LIABILITY  WILL  BE  INPUTTED 
TO  SELLER,  IS  LIMITED  TO  THE  “LIMITED  WARRANTY”  OF  REPAIR  AND/OR 
REPLACEMENT AS SO STATED IN OUR WARRANTY OF PRODUCT.  IN NO EVENT 
SHALL  THE  SELLER  BE  LIABLE  FOR  ANY  SPECIAL,  INDIRECT,  CONSEQUENTIAL 
OR  OTHER  DAMAGES  OF  A  LIKE  GENERAL  NATURE,  INCLUDING,  WITHOUT 
LIMITATION, LOSS OF PROFITS OR PRODUCTION, OR LOSS OR EXPENSES OF ANY 
NATURE INCURRED BY THE BUYER OR ANY THIRD PARTY.

UE specifications subject to change without notice

.

INTERNATIONAL OFFICES

AUSTRALIA

      United Electric Controls 

      (Australia) PTY Ltd

      Unit 2, 615 Warrigal Road

      Locked Bag 600

      Ashburton, Victoria  

      3147, Australia

      Phone: 613-9567-0750 

      FAX: 613-9567-0755
BELGIUM

      United Electric Controls-Europe

      G. Van Gervenstraat 19A

      B-9120 Beveren-Waas, Belgium

      Phone: 32-37554-383 

 

      FAX: 32-37552-747
GERMANY

      United Electric Controls

      An Der Zentlinde 21

      D-64711 Erbach, Germany

      Phone: 496-062-7400

      FAX: 496-062-7501
MALAYSIA

      United Electric Controls, Far East

      No. 1-2-2, 2nd Floor 

      Jalan 4/101C

      Cheras Business Centre

      Batu 5, Jalan Cheras

      56100 Kuala Lumpur, Malaysia

      Phone: 603-9133-4122

       FAX: 603-9133-4155
RUSSIA

       United Electric Controls, Moscow 

 

       Alyabyeva str., 4-1-4

       Moscow, 121309, Russia   

 

       Phone: +7 (095) 792-88-06 

 

       FAX: +7 (095) 142-34-60

CANADA

      

EASTERN

       68 Mosley Crescent

       Brampton, Ontario

       Canada L6Y 5C8

       Phone: 905-455-5131

       FAX: 905-455-5131

       WESTERN

       148 Silver Ridge Close N.W.

       Calgary, Alberta  

       Canada T3B 3T4

       Phone:  403-247-3724

       FAX:  403-247-3724

U.S. SALES OFFICES

       United Electric Controls

       32 Highland Rd.

       South Hampton, NH  03827

       Phone: 603-394-0078

       FAX:  603-394-0175

       United Electric Controls

       28 N. Wise Ave.

       Freeport, IL  61032

       Phone:  815-235-3501

       FAX:  815-235-3847

       United Electric Controls

       1022 Vineyard Drive

       Conyers, GA 30013

       Phone: 770-483-8400

       FAX: 770-929-8716

       United Electric Controls

       5829 Grazing Court

       Mason, OH 45040

       Phone: 513-398-3175

       FAX: 513-398-3076

       United Electric Controls 

       102 Salazar Court

       Clayton, CA 94517

       Phone: 925-524-0210

       FAX: 925-524-0210

       United Electric Controls 

       27 Summit Terrace

       Sparta, NJ 07871

       Phone: 973-271-2550

       FAX: 973-729-6099

       United Electric Controls 

       12630 Summerwood Glen

       Houston, TX 77041

       Phone: 832-243-0119

       FAX: 832-243-0140

FGS3500504

1 0 0 B - 0 2

U N I T E D   E L E C T R I C  
C O N T R O L S

180 Dexter Avenue, P.O. Box 9143
Watertown, MA  02471-9143   USA
Telephone: 617 926-1000    Fax: 617 926-2568
http://www.ueonline.com

Summary of Contents for 100 Serie

Page 1: ...NG CHECK THE SENSOR MODEL SELECTED FOR COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE SENSOR AND WETTED PARTS The H100 and H100K differential pressure switches are activated when a bellows diaphragm or piston sensor responds to a pressure change This response at a pre determined set point actuates a single snap acting switch converting the pressure signal into an electrical signal Control ...

Page 2: ...by tightening adjustment lock onto it See diagram 1 Controls include uncalibrated reference scales for high low or mid range settings Adjustable Differential Models Model 15623 and control types with option code 1519 incorporate a snap switch with internal adjustment wheel Turning this wheel raises or lowers the pressure rise set point The fall set point remains constant Consult factory for additi...

Page 3: ...6 7 56 192 0 1 2 188 189 6 62 168 1 1 2 190 194 6 63 168 4 1 2 218 274 6 56 166 6 1 4 358 376 7 03 178 6 1 4 483 486 7 56 192 0 1 2 488 489 6 62 168 1 1 2 490 494 6 63 168 4 1 2 520 525 8 44 214 4 1 2 530 535 8 00 203 2 1 2 540 548 8 34 211 8 1 8 560 564 6 62 168 1 2 Sanitary fitting 565 567 6 62 168 1 1 1 2 Sanitary fitting 610 616 7 00 177 8 1 4 680 6 97 177 0 1 4 701 706 6 57 166 9 1 4 15623 6 ...

Page 4: ...n the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and workmanship and that any such product which is found to be defective in such workmanship or ma...

Page 5: ...reeze Protection Thermostats Proof Pressures to 10 000 psi 689 5 bar Adjustable Ranges Pressure 30 Hg Vac to 5000 psi 1 to 344 7 bar wc Ranges 300 wc Vacuum to 250 wc Pressure 746 7 to 622 3 mbar Differential Pressure 0 2 wcd to 500 psid 0 5 mbar to 34 5 bar Temperature 180 to 650 F 117 8 to 343 3 C PRESSURE VACUUM DIFFERENTIAL PRESSURE AND TEMPERATURE SWITCHES 1 0 0 B 0 2 100 Series 100 Seri es ...

Page 6: ...ries are heat tracing freeze protection processing equipment pumps compressors inputs for annunciator panels and fire suppression systems overview features UL listed and cUL certified CE compliant to low voltage directive and pressure equipment directive Single switch SPDT or DPDT output Welded stainless steel diaphragm models Ultra low pressure wc models Optional sensor material for corrosive med...

Page 7: ...ly closed ELECTRICAL RATING 15 A 125 250 480 VAC resistive except for H100 15623 20A 125 250 480 VAC resistive B100 13546 and E100 13545 22A 480 VAC WEIGHT 2 7 lbs Varies with model ELECTRICAL CONNECTION 1 2 NPT female Two 7 8 diameter knockouts PRESSURE CONNECTION Models 15623 218 270 376 610 680 701 706 1 4 NPT female Models 171 194 483 494 520 535 1 2 NPT female Models 540 548 1 8 NPT female Mo...

Page 8: ...0 Vac to 10 24 9 to 24 9 0 1 to 0 6 0 2 to 1 5 50 3 4 100 6 9 532 50 Vac to 50 124 5 to 124 5 0 1 to 3 0 2 to 7 5 50 3 4 100 6 9 533 0 5 to 5 0 1 2 to 12 4 0 1 to 0 3 0 2 to 0 7 50 3 4 100 6 9 534 2 5 to 50 6 2 to 124 5 0 1 to 0 8 0 2 to 2 0 50 3 4 100 6 9 535 10 to 250 24 9 to 622 3 0 1 to 10 0 2 to 24 9 50 3 4 100 6 9 psi bar psi bar psi bar psi bar Welded 316L stainless steel diaphragm with 1 2...

Page 9: ...1 3 50 to 300 3 4 to 20 7 4000 275 8 7000 482 6 Welded 316 stainless steel diaphragm with 1 2 NPT female pressure connection large 0 72 orifice for clean out purposes Lower75 rangespan Top25 rangespan psi bar psi bar psi bar psi bar psi bar 190 5 to 30 0 3 to 2 1 1 to 3 0 07 to 0 2 6 max 0 4 1500 103 4 2500 172 4 191 10 to 100 0 7 to 6 9 1 to 8 0 07 to 0 6 15 max 1 0 1500 103 4 2500 172 4 192 15 t...

Page 10: ...0 5 2 to 68 9 30 to 150 2 07 to 10 3 6000 413 7 10 000 689 5 612 125 to 3000 8 6 to 206 8 40 to 250 2 76 to 17 2 6000 413 7 10 000 689 5 616 700 to 5000 48 3 to 344 7 40 to 375 2 76 to 25 9 6000 413 7 10 000 689 5 316 stainless steel bellows with 1 4 NPT female pressure connection Not recommended for gas applications or for rapid or high cycling pressure changes 680 100 to 1700 6 9 to 117 2 9 to 4...

Page 11: ...to 337 8 690 365 6 10 5 3 8 x 31 4 Type F100 Stainless steel bulb and capillary no reference dial 1BS 180 to 120 117 8 to 48 9 170 76 6 N A 3 8 x 33 4 2BS 125 to 350 87 2 to 176 7 400 204 4 N A 3 8 x 25 8 3BS 125 to 500 87 2 to 260 550 287 8 N A 3 8 x 21 8 4BS 40 to 120 40 to 48 9 170 76 6 N A 3 8 x 63 4 5BS 40 to 180 40 to 82 2 230 110 N A 3 8 x 5 6BS 0 to 250 17 8 to 121 1 300 148 8 N A 3 8 x 41...

Page 12: ... A 125 250 480 VAC resistive adjustment wheel changes rise setting only If adjustment on fall setting is required use primary adjustment NOT AVAILABLE TYPES B100 E100 OR MODELS 171 194 483 494 540 567 610 616 1530 External manual reset 15 A 125 250 480 VAC resistive latches on rise 1535 High ambient 15 A 125 250 VAC resistive temperatures up to 250 F 145 C NOT AVAILABLE MODELS 520 535 1537 Vapor s...

Page 13: ...WC RANGES AVAILABLE MODELS 520 525 XC001 Aluminum pressure connection Viton diaphragm Viton O ring XC002 Aluminum pressure connection Kapton diaphragm Buna N O ring XC003 Aluminum pressure connection Kapton diaphragm Viton O ring XC004 316L Stainless steel pressure connection 316L stainless steel diaphragm Viton O ring Over range pressure is limited to 100 psi XC005 316L Stainless steel pressure c...

Page 14: ...pt Model 13546 W139 SD6225 139 3 4 NPT X 1 23 32 BT BRASS W140 SD6225 140 3 4 NPT X 1 23 32 BT 316 ST ST W000 IMMERSION STEM AND THERMOWELLS Note Option W000 is a special Immersion Stem construction that has no external thread This option fits inside a special thermowell and is secured with a set screw Option Description W000 Immersion stem only Brass W097 Immersion stem and thermowell Includes W0...

Page 15: ...86 7 56 192 0 1 2 188 189 6 62 168 1 1 2 190 194 6 63 168 4 1 2 218 274 6 56 166 6 1 4 358 376 7 03 178 6 1 4 483 486 7 56 192 0 1 2 488 489 6 62 168 1 1 2 490 494 6 63 168 4 1 2 520 525 8 44 214 4 1 2 530 535 8 00 203 2 1 2 560 564 6 62 168 1 2 Sanitary Fitting 565 567 6 62 168 1 11 2 Sanitary Fitting 610 616 7 00 177 8 1 4 680 6 97 177 0 1 4 701 706 15623 6 56 166 9 1 4 Temperature 120 121 13546...

Page 16: ... storage and in any case where products are disassembled by anyone other than authorized Seller s representatives EXCEPT FOR THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE SELLER DISCLAIMS ALL WARRANTIES WHATSOEVER WITH RESPECT TO THE PRODUCT INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE LIMITATION OF SELLER S LIABILITY SELLER S LIABILITY TO...

Reviews: