GD-36
28
27
610.396A
rev.
1
7.5.1 ACTIVATION MODE
In the corresponding drop-down menu, select either Open Contact, "
OPEN CONTACT
" or Closed Contact,
"
CLOSED CONTACT
".
If "
OPEN CONTACT
" is selected, the message will start playing after opening the corresponding contact that was
previously closed.
If "
CLOSED CONACT
" is selected, the message will start playing after closing the corresponding contact that was
previously open.
7.5.2 PRIORITY MODE
In the corresponding pull-down menu, select between Geographical "
GEOGRAPHICAL
", (the highest priority is IN1
and the lowest priority is IN10), or by numerical value "
NUMERICAL
", (priority 1 is the highest and priority 10 is the
lowest).
Parameters must be specified for each of the "
REMOTE INPUT
" inputs, such as the audio file name "
MESSAGE
FILE
" and the priority "
PRIORITY LEVEL
". It is necessary to specify, at each "
INPUT
" input, whether the message
playback activation shall be triggered by an edge ("
EDGE
" or "push-button" type), or by a level change ("
LEVEL
" or
"Switch" type).
In addition, you can select the output remote controls that will be activated when this message is activated. To select
an output, press on the "
OUT
" button of the output to be activated and its corresponding any combination of outputs
can be activated.
Remember that after modifying the parameters that have an associated "
SAVE CHANGES
" button, this button must
be pressed to make the changes effective in the GD-36.
7.6 CHANGE PASSWORD
This page allows us to change the Password:
To change the password it will be necessary to enter the current password in the "
OLD PASSWORD
" box (4 numeric
digits), enter the new password in the "
NEW PASSWORD
" box (4 numeric digits), repeat the new password in the
"
REPEAT NEW PASSWORD
" box.
Do not forget to press "
SAVE PASSWORD
" to make the changes effective in the GD-36.
NOTE
: Remember that the default password is 1234.