Ubiflux W180 / W180+
37
Setting values
Chapter 13
STEP
NO. DESCRIPTION
FACTORY SET-
TINGS “+”
SETTING RANGE
STEP
DISPLAY TEXT +
SYMBOLS
20 Exhaust fan mode
switching input 1
5
0
(= Exhaust fan off)
1
(= Absolute min. flowrate 50 m
3
/h)
2
(= Flowrate setting 1)
3
(= Flowrate setting 2)
4
(= Flowrate setting 3)
5
(= Multiple switch)
6
(= Maximum flowrate
7
(= No signal exhaust fan)
CN1
21 Selection input 2
1
0 (= NO contact)
1 (= 0 - 10 V input)
2
= NC contact)
3 (= switching output 2/ bypass active
12V;
bypass not active
0V)
4 (= switching output 2/ bypass active
0V;
bypass not active
12V)
V2
22 Minimum voltage input 2
0.0 V
0.0 V - 10.0 V
0.5 V V2 MIN
23 Maximum voltage input 2
10.0 V
0.0 V - 10.0 V
0.5 V V2 MAX
24 Conditions
switching input 2
0
0
(= Off)
1
(= On)
2
(= On if conditions
bypass function active)
3
(= Bypass function control)
4
(= Bedroom diffuser)
CN2
25 Supply fan mode
switching input 2
5
0
(= Supply fan off)
1
(= Absolute min. flowrate 50 m
3
/h)
2
(= Flowrate setting 1)
3
(= Flowrate setting 2)
4
(= Flowrate setting 3)
5
(= Multiple switch)
6
(= Maximum flowrate)
7
(= No signal supply fan)
CN2
26 Exhaust fan mode
switching input 2
5
0
(= Exhaust fan off)
1
(= Absolute min. flowrate 50 m
3
/h)
2
(= Flowrate setting 1)
3
(= Flowrate setting 2)
4
(= Flowrate setting 3)
5
(= Multiple switch)
6
(= Maximum flowrate)
7
(= No signal exhaust fan)
CN2
27 Geo-heat exchanger
OFF
OFF
(= Diffuser control geo-heat
exchanger off)
ON
(= Diffuser control geo-heat
exchanger on)
EWT
28
Minimum temperature
geo-heat exchanger
(Below this temperature
the diffuser opens.)
5.0 °C
0.0°C - 10.0°C
0.5 °C EWT T-
29
Maximum temperature
geo-heat exchanger
(Above this temperature
the diffuser opens.)
25.0 °C
15.0°C - 40.0°C
0.5 °C EWT T+
30 RH sensor
OFF
OFF
(= RH sensor switched off)
ON
(= RH sensor switched on)
31 Sensitivity
RH sensor
0
-2
most sensitive
-1
↑
0
basic setting RH sensor
+1
↓
+2
least sensitive