Instelwaarden/ Setting values/ Einstellwerte
Valeurs de réglage
Modifications reserved
Ubbink continuously strives after improvement of products and reserves the right to change the specifications
without prior notice.
STEP NO. DESCRIPTION
FACTORY SETTING
Ubiflux F150 PLUS
ADJUSTING RANGE
STEP
19
Selection input 2
1
0 (= normally open contact)
1 (= 0 - 10V input active)
2 (= normally closed contact)
3 (= input 2/ bypas open
12V;
bypass closed
0V)
4 (= input 2/ bypas open
0V;
bypass closed
12V)
20
Minimum voltage input 2
0,0 V
0,0 Volt - 10,0 Volt
0,5 V
21
Maximum voltage input 2
10,0 V
0,0 Volt- 10,0 Volt
0,5 V
22
Conditions
switching input 2
0
0 (= Off)
1 (= On)
2 (= On if conditions bypass open satisfied)
3 (= Bypass control)
4 (= Bedroom valve)
23
Supply fan mode
switching input 2
5
0 (= Input fan off)
1 (= Absolute min. flow rate 30 m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No input fan activation)
24
Extract fan mode
switching input 2
5
0 (= Extract fan off)
1 (= Absolute min. flow rate 50m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No extract fan activation)
25
Geo heat exchanger
OFF
OFF (= Valve control geo heat
exchanger off)
ON (= Valve control geo heat
exchanger on)
26
Minimum temperature
geo heat exchanger
(Below this temperature
the valve opens.)
5,0 °C
0,0 °C - 10,0 °C
0,5 °C
27
Maximum temperature
geo heat exchanger
(Above this temperature
the valve opens.)
25,0 °C
15,0 °C - 40,0 °C
0,5 °C
STEP NO. DESCRIPTION
FACTORY SETTING
Ubiflux F150
ADJUSTING RANGE
STEP
28
RH-sensor
OFF
OFF
(= RH-sensor not active)
ON
(= RH-sensor active)
29
Sensitivity
RH-sensor
0
+2
most sensitive
+1
↑
0
default setting RH-sensor
-1
↓
-2
least sensitive