-4-
FLOOR PROTECTOR DIMENSIONS
H
J
K
L
M
N
P
Q
Key
Dimension
Inch
mm
H
Stove Width
22.48
571
J
Stove Depth
20.76
528
*K
Front
16
407
L
Back
2
51
M Left
8
204
N
Right
8
204
P Total Width
38.48
978
Q Total Length
38.76
985
* Canadian installations require 18” (457mm)
FREE STANDING STOVE CLEARANCES
A wood stove must never be installed in a hallway or near a staircase, since it may block the way in case of fire
or fail to respect required clearances. It is of utmost importance that the clearances to combustible materials be
strictly adhered to during installation of the stove. Refer to the tables below:
•
Do not place any combustible material within 4’ (1.2m) of the front of the unit.
•
The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue pipe.
•
The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
floor, or a ceiling.
•
For Canadian installations, where passage through a wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
•
A flue pipe crossing a combustible wall must have a minimum clearance of 18” (457.2mm).
•
To reduce flue clearances from combustible materials, contact your local safety department.
Key
Dimensions
Inch
mm
A
Backwall to Stove
17
432
B
Sidewall to Stove
21
534
C
Wall to corner (Angled Installation)
14
356
D
Ceiling Height
84
2134
E
Backwall to Flue
20
508
F
Sidewall to Flue
29
737
G
Wall to Flue (Angled Installation)
22
559
CLEARANCE TO WALLS
Side w
all
Backwall
Side w
all
Backwall
CORNER INSTALLATION
CLEARANCE TO WALLS
Ceiling
CORNER INSTALLATION
CLEARANCE TO
WALLS & CELING