Part # 1382692 Rev 3 (02/22/08)

Page 5

INSTALLATION Continued

Standards

Installation must be planned in accordance with all 
applicable state and local codes, taking into account the 
following standards (or latest edition):

Grease Extractor ANSI/NFPA 96-1992

Power Ventilators ANSI/NFPA 96-1987

Filter Unit ANSI/NFPA 96-1987

Smoke Detectors ANSI/NFPA 728-1986. CAN/ULC 8553-
1986

Fire Extinguisher (C02) ANSI/NFPA 12-1989

This section is not intended to be complete and other 
nationally recognized standards may be appropriate.

Gas Supply

1.  Installation of the equipment should be made by a 

licensed plumber.

2.  A gas shut-off valve must be installed in the gas supply 

line ahead or the appliance for safety and for ease of 
future service.

3.  A gas pressure regulator must be installed at the 

appliance prior to connecting the equipment to the gas 
line. Failure to install a regulator will void the equipment 
warranty.

NOTE: The gas supply (service) line must be the same size or 
greater than the inlet line of the appliance. U.S. Range “Regal” 
char-broilers use a 3/4” NPT inlet. Sealant on all pipe joints 
must be resistive to LP gas.

To convert to propane or natural gas, contact a certified 
service agency.

Statutory Regulations 

Safe and satisfactory operation of your equipment depends, 
to a great extent, on its proper installation. Installation must 
conform to local codes or, in the absence of local codes with 
the National Fuel code, ANSI Z223.1, Natural Gas Installation 
Code, CAN/CGA-B149.1, or the Propane Installation Code, 
CAN/CGA-B149.2, as applicable, including:

1.  The appliance and its individual shutoff valve must be 

disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 1/2 psi (3.45 kPa).

2.  The appliance must be isolated from the gas supply 

piping system by closing its individual manual shutoff 
valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 psi (3.45 
kPa)

Manual Shut-Off Valve

This installer-supplied valve must be installed in the gas 
service line ahead of the appliance and regulator in the gas 
stream and in a position where it can be reached quickly in 
the event of an emergency.

Pressure Regulator

All commercial cooking equipment must have a pressure 
regulator on the incoming service line for safe and efficient 
operation. The pressure regulator installed must be listed by 
a nationally recognized agency. Line service pressure may 
fluctuate with local demand.

All “Regal” char-broilers must be installed with the included 
gas pressure regulator.

Regulators are adjusted at the factory for 5” WC (natural gas) 
or 10” WC (LP gas) depending on the customer’s ordering 
instructions.

Prior to connecting the regulator, check the incoming line 
pressure, as these regulators can withstand a maximum 
pressure of 1/2 psi (14” WC). If the Line pressure is beyond 
this limit, a step-down regulator will be required. Double-
check the arrow forged onto the bottom of the regulator 
body which shows gas flow directions; it should point 
downstream to the appliance. The red air-vent cap is part of 
the regulator and should not be removed unless local codes 
require external venting.

Regulators can be adjusted in the field, but it is 
recommended that they not be tampered with unless that 
part is known to be out of adjustment or serious pressure 
fluctuations are found to exist and can be solved no other 
way. Any adjustments to regulators must be made by 
qualified service personnel with proper test equipment.

If a vent line from the gas appliance pressure regulator is 
used, it should be installed to the outdoors in accordance 
with local codes or code ANSI Z223.1, Natural Gas Installation 
code, CAN/CGA-B149.1, or The Propane Installation code, 
CAN/CGA-B149.2.

Summary of Contents for "REGAL"SERIES RADIANT CHAR-BROILERS

Page 1: ...ississauga Ontario L4W 1X4 CANADA Phone 905 624 0260 Fax 905 624 5669 Enodis UK LTD Swallowfield Way Hayes Middlesex UB3 1DQ ENGLAND Telephone 081 561 0433 Fax 081 848 0041 Part 1382692 Rev 3 02 22 08...

Page 2: ...could expose you to airborne particles of glass wool ceramic fibers Inhalation of airborne particles of glass wool ceramic fibers is known to the state of California to cause cancer Operation of this...

Page 3: ...ntilation 4 Standards 5 Gas Supply 5 Statutory Regulations 5 Manual Shut Off Valve 5 Pressure Regulator 5 Rigid Connections 6 Flexible Couplings Connectors 6 Manual Pilot Valve 6 Testing and Adjustmen...

Page 4: ...only with four inch high adjustable legs 3 Zero clearance is required from non combustible construction at sides and rear Adequate clearances must be maintained at all times in front and at the sides...

Page 5: ...om the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psi 3 45 kPa Manu...

Page 6: ...with constant burning pilots These should be manually lighted immediately after the gas is turned on and the system is checked for leaks Pilots can be reached with a long match or taper down from the...

Page 7: ...to re light the pilots several times until the new lines are purged of any trapped air and constant gas flow is attained Final Preparation New units are wiped clean with solvents at the factory to rem...

Page 8: ...er Weekly If a daily maintenance is performed as recommended above weekly maintenance will not be required beyond the daily cleaning for the last day of the working week Periodic Your U S Range Regal...

Page 9: ...Part 1382692 Rev 3 02 22 08 Page 9...

Page 10: ......

Page 11: ......

Page 12: ...92 Rev 3 02 22 08 Page 9 SERVICE ET PI CES L installation l entretien et les r parations devront tre eff ectu s par l agence de service U S Range locale autoris e dont le nom fi gure dans le manuel d...

Page 13: ...de 3 5 8 po faisant toute la largeur de la partie carrel e Le reste de la graisse s gouttant des radiants est collect dans une seconde l chefrite qui recouvre le reste du fond du grilloir Il est n ces...

Page 14: ...intensit voulue 8 Ouvrez le robinet du br leur principal et v rifi ez qu il s enfl amme bien partir de la veilleuse puis arr tez le br leur 9 R p tez les tapes 6 8 pour allumer les autres veilleuses S...

Page 15: ...Connecteurs Si l appareil doit tre install avec des accouplements fl exibles et ou des raccords rapides l installateur doit utiliser un connecteur fl exible approuv AGA de qualit commerciale ou au min...

Page 16: ...s Regal sont munis d une prise de 3 4 po NPT Le produit d tanch it sur tous les joints doivent r sister au gaz de p trole liqu fi Pour proc der la conversion au propane ou au gaz naturel veuillez cont...

Page 17: ...gagement La zone d installation de l appareil doit tre gard e libre et exempte de toute mati re combustible Par sa conception cet appareil est destin aux installations suivantes 1 Pour installation da...

Page 18: ...s 5 Alimentation En Gaz 5 R glementation L gale 5 Robinet D arr t Manuel 5 R gulateur De Pression 5 Connexions Rigides 6 Accouplements Flexibles Connecteurs 6 Robinet De Veilleuse Manuel 6 Essais Et R...

Page 19: ...ssi res de laine de verre fibres c ramiques L inhalation de ces particules de laine de verre ou de fibres c ramiques est reconnue par l tat de Californie comme causant le cancer L utilisation de ce pr...

Page 20: ...L4W 1X4 CANADA T l phone 905 624 0260 T l copieur 905 624 5669 Enodis UK LTD Swallowfi eld Way Hayes Middlesex UB3 1DQ ANGLETERRE T l phone 081 561 0433 T l copieur 081 848 0041 Pi ce n 1382692 Rev 3...

Reviews: