78
107362-01 - 8/17
3) Indirect Water Heater Loop Piping – If an indirect water heater is used, install it as shown in Figure 9.7b, 9.7c, 9.8b, 9.8c.
Refer to the indirect water heater installation manual for the proper sizing the indirect water heater loop pump and piping.
4) Hydraulic Separators – Hydraulic separators serve the same purpose as the closely spaced tees connecting the boiler
and system loops. They also generally provide effective connection points for automatic air elimination devices and an
expansion tank. These separators are available from several sources and may be used in place of the closely spaced tees.
Select a hydraulic separator having 1" or larger boiler connections that is designed for the boiler flow rates shown in Table
9.3.
IX. System Piping
(continued)
Table 9.6: Fitting and Valve Equivalent Length
Copper Fitting and Sweat Valve
Equivalent Length (Ft)
Fitting or Valve
Description
Copper Pipe or Valve Size
1
1¼
1½
2
90° Elbow
2.5
3.0
4.0
5.5
45° Elbow
1.0
1.2
1.5
2.0
Tee (through flow)
0.5
0.6
0.8
1.0
Tee (Branch flow)
4.5
5.5
7.0
9.0
Diverter Tee (typical)
23.5
25.0
23.0
23.0
Gate Valve
0.3
0.4
0.5
0.7
Globe Valve
25.0
36.0
46.0
56.0
Angle Valve
5.3
7.8
9.4
12.5
Ball Valve (standard port)
4.3
7.0
6.6
14.0
Ball Valve (full port)
1.9
1.4
2.2
1.3
Y-Strainer
*
7.0
Swing Check Valve
4.5
5.5
6.5
9.0
Flow-Check Valve
(typical)
54.0
74.0
57.0
177.0
Butterfly Valve
2.7
2.0
2.7
4.5
*
Based on Cv of 20. Pressure drop through strainers varies widely. 7 ft. equ length
may be assumed for strainers having a published Cv greater than 10.
NOTE:
Table 9.3 is provided as reference to assist in piping design and specifies equivalent
length of typical piping fittings and valves.
Summary of Contents for ASPEN ASPN-085
Page 94: ...94 107362 01 8 17 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued...
Page 95: ...95 107362 01 8 17 PAGE LEFT INTENTIONALLY BLANK...
Page 96: ...96 107362 01 8 17 X Wiring continued CONDENSATE FLOAT SWITCH...
Page 97: ...97 107362 01 8 17 X Wiring continued Figure 10 6 Internal Wiring Connections Diagram...
Page 106: ...106 107362 01 8 17 Operating Instructions XI Start Up and Checkout continued...
Page 160: ...160 107362 01 8 17 XV Service Parts continued All models 5G 5F 5B 5A 5D 5E 5C 5D...
Page 179: ...179 107362 01 8 17...