13
2.
If DHCP mode is ON, the dynamic IP address obtain routine will start
3.
The panel automatic configuration mode starts if the access control system
IP address (IP or DNS name) is not set:
a.
Panel sends data packages announcing access control system
server about itself as a new device in the local network
Despite it is broadcast announcement, it is limited with single
range local network and active network equipment. That’s why
the IP addresses of the access control system server are to be
set manually for networks with sophisticated topology.
b.
The system will warn operator after the receiving of the data
package from the new panel. Operator must add panel to the
system database (DB).
c.
After the panel added to the DB it receives the answer from the
access control system server. The address of the access control
system server recorded into the control panel and it stops to
broadcast.
d.
Operator has to upload panel after its adjustment recorded into
the DB. Panel becomes associated to the certain access control
system server, eliminating panel control capture with another
system.
Return panel to the factory settings to eliminate the panel
association to the system
e.
In the case of access control system server IP address change
panel will initiate the automatic configuration routine, but the data
exchange will be possible with previously connected system only.
Interaction with elevator equipment
U-Prox WRS485 interface convertor connected to the U-Prox IC E control panel to
provide the noise-resistant and long-range RS-485 interface to the reader, placed in
elevator cabin.
To control the loops of the floor selection buttons up to four U-Prox RM relay
modules connected to the U-Prox IC E control panel. The U-Prox RM relay terminals
connected in series with buttons’ terminals. Connect relay terminals in way that
provides the floor selection buttons operation in case of U-Prox RM power failure.
Z1…Z8 zone loops used for floor selection buttons state supervision and for buttons
remote connection control. On pressing floor selection button U-Prox IC E
generates message "Access granted to the floor."