Tr
oubleshooting
Page 80
5.8 EC (Refrigerant Leakage Detection diagnosis and solution)
Description
: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.
In the beginning 8 minutes after the compressor starts up, if T2
<
Tcool-1°C does not keep continuous 4 seconds and
compressor running frequency higher than 50Hz does not keep continuous 3 minutes, and this situation happens 3
times, the display area will show “EC” and AC will turn off.
Recommended parts to prepare:
• Faulty T2 sensor
• Faulty indoo
r PCB
• System problems, such as leakage or blockages
Troubleshooting and repair
:
Power off, then restart the unit 2 minutes later.
Are any leakages
present?
Check System for blockages and
clear blockages if present.
Does a problem remain?
Put your hands in front of the
indoor air outlet.
YES
Is there cool
air blowing out from
indoor air outlet?
Is it securely
attached?
Replace the
indoor PCB
YES
Check the T2 sensor.
YES
Check system for leakages.
NO
NO
Repair the leakage and
recharge the refrigerant.
YES
NO
Summary of Contents for TS2MVI32-09
Page 1: ...ENGLISH SERVICE MANUAL TS2ΜVI32 09 TS2MVO32 09 TS2ΜVI32 12 TS2MVO32 12 ...
Page 2: ......
Page 4: ......
Page 5: ...Contents 1 Precautions 2 2 Information servicing 3 Safety Precautions ...
Page 50: ...Maintenance and Disassembly Page 46 ...
Page 87: ......