Tyco TY-FRB Series Manual Download Page 9

TFP682

Page 9 of 10

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for 

availability. When placing an order, 

indicate the full product name and Part 

Number (P/N).

Sprinkler Assemblies

Specify: (specify SIN), (specify Stan-

dard Response or Quick Response), 

(specify K-factor), (specify) tempera-

ture rating, (specify Upright, Pendent 

or HSW), P/N (specify from Table D)

Recessed Escutcheon

Specify: Style (specify 10 or 40) 

Recessed Escutcheon, Grey Aluminum 

(RAL9007) finish, P/N (specify*)

*Refer to Technical Data Sheet TFP770.

Sprinkler Wrench

Specify: W-Type 6 Sprinkler Wrench, 

P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler 

Wrench, P/N 56-850-4-001

Care and 

Maintenance

The TYCO Series TY-B and TY-FRB 

Sprinklers must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection system must be 

obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
The owner must assure that the sprin-

klers are not used for hanging of any 

objects; otherwise, non-operation in 

the event of a fire or inadvertent oper-

ation may result.
Absence of an escutcheon, which is 

used to cover a clearance hole, may 

delay the time to sprinkler operation in 

a fire situation.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. For more informa-

tion, see the Installation section.
Frequent visual inspections are rec-

ommended to be initially performed 

for corrosion resistant sprinklers, after 

the installation has been completed, 

to verify the integrity of the corrosion 

resistant material of construction. 

Thereafter, annual inspections accord-

ing to NFPA 25 should suffice; however, 

instead of inspecting from the floor 

level, a random sampling of close-up 

visual inspections should be made, so 

as to better determine the exact sprin-

kler condition and the long term integ-

rity of the corrosion resistant material 

of construction, as it may be affected 

by the corrosive conditions present.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associ-

ation such as NFPA 25, in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
Automatic sprinkler systems should be 

inspected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

P/N  57  —  XXX  —  X  —  XXX

Standard Response (SR)

SIN

570

TY-B 5.6K Upright SR

TY3151

 590

TY-B 8.0K Upright SR

TY4151

571

TY-B 5.6K Pendent SR

TY3251

591

TY-B 8.0K Pendent SR

TY4251

578

TY-B 5.6K HSW SR

TY3351

Quick Response (QR)

SIN

370

TY-FRB 5.6K Upright QR

TY3131

390

TY-FRB 8.0K Upright QR

TY4131

371

TY-FRB 5.6K Pendent QR

TY3231

391

TY-FRB 8.0K Pendent QR

TY4231

378

TY-FRB 5.6K HSW QR

TY3331

Sprinkler Finish

2

Grey Aluminium (RAL9007)

Temperature Rating

135

135°F (57°C)

155

155°F (68°C)

175

175°F (79°C)

200

200°F (93°C)

286

286°F (141°C)

360

360°F (182°C)*

* TY-B - Only

TABLE D 

POLY-STAINLESS SERIES TY-B AND TY-FRB 

UPRIGHT, PENDENT AND HORIZONTAL SIDEWALL SPRINKLERS 

PART NUMBER SELECTION

Summary of Contents for TY-FRB Series

Page 1: ...ent Sprinklers The upright and pendent sprinklers are standard coverage spray sprinklers available in either 5 6 or 8 0 K factor The recessed version is intended for use in areas with a finished ceiling The two piece Style 10 1 2 inch NPT or Style 40 3 4 inch NPT recessed escutcheons provide 1 2 inch 12 7 mm of recessed adjustment or 3 4 inch 19 1 mm of total adjustment from the flush pendent posi...

Page 2: ...ecognized by the applicable Listing or Approval agency for example the UL Listing is based on the requirements of NFPA 13 Only the Style 10 or 40 Recessed Escutcheon as applicable is to be used for recessed installation Model K Factor Response Type Temperature Rating Bulb Liquid Color Sprinkler Material Brass TY B 5 6 1 2 in NPT SR Upright TY3151 and Pendent TY3251 135 F 57 C Orange 1 2 3 155 F 68...

Page 3: ...6 F 141 C Blue TY FRB 8 0 3 4 in NPT QR Upright TY4131 and Pendent TY4231 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Recessed Pendent TY4231 See Figure 4 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue NOTES 1 UL Listed 2 C UL Listed 3 EAC Approved Installed with Style 10 1 2 NPT Recessed Escutcheon Installed with Style...

Page 4: ... 93 C Green 286 F 141 C Blue TY FRB 5 6 1 2 in NPT QR Horizontal Sidewall TY3331 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Recessed Horizontal Sidewall TY3331 See Figure 6 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue NOTES 1 UL Listed 2 C UL Listed 3 EAC Approved Installed with Style 10 1 2 NPT Recessed Escutcheon T...

Page 5: ...55 6 mm ESCUTCHEON PLATE SEATING SURFACE STYLE 10 RECESSED ESCUTCHEON 4 6 5 1 3 2 2 7 8 73 0 mm DIA UPRIGHT CROSS SECTION PENDENT RECESSED PENDENT 3 1 5 4 2 6 Sealing Assembly Compression Screw Temperature rating indicated on Deflector Frame Bulb Button Deflector WRENCH FLATS ESCUTCHEON PLATE SEATING SURFACE 3 4 NPT 2 1 4 57 2 mm 1 9 16 39 7 mm 2 5 16 58 7 mm 1 2 12 7 mm NOMINAL MAKE IN STYLE 40 R...

Page 6: ... the sprinkler by under or over tightening the sprin kler Re adjust the position of the sprin kler fitting to suit UPRIGHT CROSS SECTION PENDENT RECESSED PENDENT 6 4 3 2 1 5 Temperature rating indicated on Deflector Sealing Assembly Compression Screw Frame Bulb Button Deflector WRENCH FLATS ESCUTCHEON PLATE SEATING SURFACE 3 4 NPT 2 1 4 57 2 mm 1 9 16 39 7 mm 2 5 16 58 7 mm 1 2 12 7 mm NOMINAL MAK...

Page 7: ...lar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2C With pipe thread sealant applied to the sprinkler threads hand tighten the sprinkler into the sprinkler fitting Step 3C Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench as shown in Figure 10 Apply the W Type 6 Sprinkler Wrench to the wrench ...

Page 8: ...m 2 1 4 DIA 57 2 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 5 8 1 4 15 9 6 4 mm MOUNTING PLATE 1 8 3 2 mm CLOSURE 13 16 20 6 mm 1 5 16 33 3 mm 1 4 6 4 mm 3 4 19 1 mm TY4231 or TY4251 FIGURE 7 POLY STAINLESS SERIES TY B OR TY FRB RECESSED PENDENT 5 6 K FACTOR 1 2 INCH NPT SPRINKLER ASSEMBLY WITH TWO PIECE 3 4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON FIGURE 8 POLY STAINLESS SERIES TY B ...

Page 9: ...damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like must be replaced Also replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb For more informa tion see the Installation section Frequent visual inspections are rec ommended to be initially performed for corrosion resistant sprinklers ...

Page 10: ... Protection Association TEFLON is a trademark of The Chemours Company FC LLC 1467 Elmwood Avenue Cranston RI 02910 Telephone 1 401 781 8220 2022 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...