![Tyco TY-FRB Series Manual Download Page 9](http://html.mh-extra.com/html/tyco/ty-frb-series/ty-frb-series_manual_1185851009.webp)
TFP682
Page 9 of 10
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies
Specify: (specify SIN), (specify Stan-
dard Response or Quick Response),
(specify K-factor), (specify) tempera-
ture rating, (specify Upright, Pendent
or HSW), P/N (specify from Table D)
Recessed Escutcheon
Specify: Style (specify 10 or 40)
Recessed Escutcheon, Grey Aluminum
(RAL9007) finish, P/N (specify*)
*Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler
Wrench, P/N 56-850-4-001
Care and
Maintenance
The TYCO Series TY-B and TY-FRB
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent oper-
ation may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more informa-
tion, see the Installation section.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant sprinklers, after
the installation has been completed,
to verify the integrity of the corrosion
resistant material of construction.
Thereafter, annual inspections accord-
ing to NFPA 25 should suffice; however,
instead of inspecting from the floor
level, a random sampling of close-up
visual inspections should be made, so
as to better determine the exact sprin-
kler condition and the long term integ-
rity of the corrosion resistant material
of construction, as it may be affected
by the corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
P/N 57 — XXX — X — XXX
Standard Response (SR)
SIN
570
TY-B 5.6K Upright SR
TY3151
590
TY-B 8.0K Upright SR
TY4151
571
TY-B 5.6K Pendent SR
TY3251
591
TY-B 8.0K Pendent SR
TY4251
578
TY-B 5.6K HSW SR
TY3351
Quick Response (QR)
SIN
370
TY-FRB 5.6K Upright QR
TY3131
390
TY-FRB 8.0K Upright QR
TY4131
371
TY-FRB 5.6K Pendent QR
TY3231
391
TY-FRB 8.0K Pendent QR
TY4231
378
TY-FRB 5.6K HSW QR
TY3331
Sprinkler Finish
2
Grey Aluminium (RAL9007)
Temperature Rating
135
135°F (57°C)
155
155°F (68°C)
175
175°F (79°C)
200
200°F (93°C)
286
286°F (141°C)
360
360°F (182°C)*
* TY-B - Only
TABLE D
POLY-STAINLESS SERIES TY-B AND TY-FRB
UPRIGHT, PENDENT AND HORIZONTAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION