TFP682

Page 8 of 10

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

5/8±1/4"

(15,9±6,4 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

3/4" (19,1 mm)

1-1/4" (31,8 mm)

1/4" (6,4 mm)

3/4" (19,1 mm)

CLOSURE

TY3331 or

TY3351

RECESS

WRENCH

WITH SPRINKLER

ENGAGEMENT

IN TO ENSURE

WRENCHING AREA

PUSH WRENCH

WRENCH RECESS

(END "A" USED FOR

1/2" NPT MODELS)

WRENCH RECESS

(END "B" USED FOR

3/4" NPT MODELS)

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

5/8±1/4"

(15,9±6,4 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

CLOSURE

1-1/4" (31,8 mm)

3/4" (19,1 mm)

3/4" (19,1 mm)

1/4" (6,4 mm)

TY3231 or

TY3251

2-7/8" DIA.

(73,0 mm)

2-1/4" DIA.

(57,2 mm)

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

5/8±1/4"

(15,9±6,4 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

CLOSURE

13/16" (20,6 mm)

1-5/16" (33,3 mm)

1/4" (6,4 mm)

3/4" (19,1 mm)

TY4231 or

TY4251

FIGURE 7 

POLY-STAINLESS SERIES TY-B OR TY-FRB 

RECESSED PENDENT 5.6 K-FACTOR 1/2 INCH NPT 

SPRINKLER ASSEMBLY 

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT 

STYLE 10 RECESSED ESCUTCHEON

FIGURE 8 

POLY-STAINLESS SERIES TY-B OR TY-FRB 

RECESSED PENDENT 8.0 K-FACTOR 3/4 INCH NPT 

SPRINKLER ASSEMBLY 

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT 

STYLE 40 RECESSED ESCUTCHEON

FIGURE 9 

POLY-STAINLESS SERIES TY-B OR TY-FRB 

RECESSED HORIZONTAL SIDEWALL 

5.6 K-FACTOR 1/2 INCH NPT 

SPRINKLER ASSEMBLY 

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT 

STYLE 10 RECESSED ESCUTCHEON

FIGURE 10 

W-TYPE 6 SPRINKLER WRENCH

FIGURE 11 

W-TYPE 7 SPRINKLER WRENCH

Summary of Contents for TY-FRB Series

Page 1: ...ent Sprinklers The upright and pendent sprinklers are standard coverage spray sprinklers available in either 5 6 or 8 0 K factor The recessed version is intended for use in areas with a finished ceiling The two piece Style 10 1 2 inch NPT or Style 40 3 4 inch NPT recessed escutcheons provide 1 2 inch 12 7 mm of recessed adjustment or 3 4 inch 19 1 mm of total adjustment from the flush pendent posi...

Page 2: ...ecognized by the applicable Listing or Approval agency for example the UL Listing is based on the requirements of NFPA 13 Only the Style 10 or 40 Recessed Escutcheon as applicable is to be used for recessed installation Model K Factor Response Type Temperature Rating Bulb Liquid Color Sprinkler Material Brass TY B 5 6 1 2 in NPT SR Upright TY3151 and Pendent TY3251 135 F 57 C Orange 1 2 3 155 F 68...

Page 3: ...6 F 141 C Blue TY FRB 8 0 3 4 in NPT QR Upright TY4131 and Pendent TY4231 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Recessed Pendent TY4231 See Figure 4 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue NOTES 1 UL Listed 2 C UL Listed 3 EAC Approved Installed with Style 10 1 2 NPT Recessed Escutcheon Installed with Style...

Page 4: ... 93 C Green 286 F 141 C Blue TY FRB 5 6 1 2 in NPT QR Horizontal Sidewall TY3331 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Recessed Horizontal Sidewall TY3331 See Figure 6 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue NOTES 1 UL Listed 2 C UL Listed 3 EAC Approved Installed with Style 10 1 2 NPT Recessed Escutcheon T...

Page 5: ...55 6 mm ESCUTCHEON PLATE SEATING SURFACE STYLE 10 RECESSED ESCUTCHEON 4 6 5 1 3 2 2 7 8 73 0 mm DIA UPRIGHT CROSS SECTION PENDENT RECESSED PENDENT 3 1 5 4 2 6 Sealing Assembly Compression Screw Temperature rating indicated on Deflector Frame Bulb Button Deflector WRENCH FLATS ESCUTCHEON PLATE SEATING SURFACE 3 4 NPT 2 1 4 57 2 mm 1 9 16 39 7 mm 2 5 16 58 7 mm 1 2 12 7 mm NOMINAL MAKE IN STYLE 40 R...

Page 6: ... the sprinkler by under or over tightening the sprin kler Re adjust the position of the sprin kler fitting to suit UPRIGHT CROSS SECTION PENDENT RECESSED PENDENT 6 4 3 2 1 5 Temperature rating indicated on Deflector Sealing Assembly Compression Screw Frame Bulb Button Deflector WRENCH FLATS ESCUTCHEON PLATE SEATING SURFACE 3 4 NPT 2 1 4 57 2 mm 1 9 16 39 7 mm 2 5 16 58 7 mm 1 2 12 7 mm NOMINAL MAK...

Page 7: ...lar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2C With pipe thread sealant applied to the sprinkler threads hand tighten the sprinkler into the sprinkler fitting Step 3C Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench as shown in Figure 10 Apply the W Type 6 Sprinkler Wrench to the wrench ...

Page 8: ...m 2 1 4 DIA 57 2 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 5 8 1 4 15 9 6 4 mm MOUNTING PLATE 1 8 3 2 mm CLOSURE 13 16 20 6 mm 1 5 16 33 3 mm 1 4 6 4 mm 3 4 19 1 mm TY4231 or TY4251 FIGURE 7 POLY STAINLESS SERIES TY B OR TY FRB RECESSED PENDENT 5 6 K FACTOR 1 2 INCH NPT SPRINKLER ASSEMBLY WITH TWO PIECE 3 4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON FIGURE 8 POLY STAINLESS SERIES TY B ...

Page 9: ...damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like must be replaced Also replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb For more informa tion see the Installation section Frequent visual inspections are rec ommended to be initially performed for corrosion resistant sprinklers ...

Page 10: ... Protection Association TEFLON is a trademark of The Chemours Company FC LLC 1467 Elmwood Avenue Cranston RI 02910 Telephone 1 401 781 8220 2022 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...