Upright and Pendent Sprinklers

The Poly-Stainless Series TY-B and 

TY-FRB Upright and Pendent Sprin-

klers must be installed in accordance 

with the following instructions:

Step 1A.

 Upright sprinklers must be 

installed in the upright position, and 

pendent sprinklers are to be installed 

in the pendent position.

Step 2A.

 With pipe thread sealant 

applied to the pipe threads, hand 

tighten the sprinkler into the sprinkler 

fitting.

Step 3A.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

6 Sprinkler Wrench, refer to Figure 10. 

With reference to Figures 1, 2, 3, and 4, 

apply the W-Type 6 Sprinkler Wrench to 

the sprinkler wrench flats.

Recessed Pendent Sprinklers

The Poly-Stainless Series TY-B and 

TY-FRB Recessed Pendent Sprinklers 

must be installed in accordance with 

the following instructions:

Step 1B. 

After installing the Style 10 

or 40 Mounting Plate, as applicable, 

over the sprinkler threads and with 

pipe sealant applied to the sprinkler 

threads, hand tighten the sprinkler into 

the sprinkler fitting.

Step 2B.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

7 Recessed Sprinkler Wrench, refer to  

Figure 11. With reference to Figures 

1, 2, 3, and 4 apply the W-Type 7 

Recessed Sprinkler Wrench to the 

sprinkler wrench flats.

Step 3B. 

After the ceiling has been 

installed or the finish coat has been 

applied, slide the Style 10 or 40 Closure 

over the sprinkler and push the Closure 

over the Mounting Plate until it comes 

in contact with the ceiling mounting 

surface.

Horizontal Sidewall Sprinklers

The Poly-Stainless Series TY-B and 

TY-FRB Horizontal Sprinklers must be 

installed in accordance with the follow-

ing instructions:

Step 1C.

 Horizontal sprinklers must 

be positioned in the horizontal position 

with their centerline of waterway per-

pendicular to the back wall and parallel 

to the ceiling. The word “TOP” on the 

deflector is to face towards the ceiling.

Step 2C.

 With pipe thread sealant 

applied to the sprinkler threads, hand 

tighten the sprinkler into the sprinkler 

fitting.

Step 3C.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

6 Sprinkler Wrench, as shown in Figure 

10. Apply the W-Type 6 Sprinkler 

Wrench to the wrench flats shown in 

Figure 5 and Figure 6.

Recessed Horizontal Sidewall 

Sprinklers

The Poly-Stainless Series TY-B and 

TY-FRB Recessed Horizontal Sidewall 

Sprinklers must be installed in accor-

dance with the following instructions:

Step 1E. 

Recessed horizontal sidewall 

sprinklers are to be positioned in the 

horizontal position with their centerline 

of waterway perpendicular to the back 

wall and parallel to the ceiling. The 

word “TOP” on the deflector is to face 

towards the ceiling.

Step 2E. 

After installing the Style 10 

Mounting Plate over the sprinkler 

threads and with pipe thread sealant 

applied to the sprinkler threads, hand 

tighten the sprinkler into the sprinkler 

fitting.

Step 3E.

 Tighten the sprinkler into the 

sprinkler fitting using only the W-Type 

7 Recessed Sprinkler Wrench, refer to 

Figure 11. Apply the W-Type 7 Sprinkler 

Wrench to the wrench flats shown in 

Figure 5 and Figure 6.

Step 4E.

 After the wall has been 

installed or the finish coat has been 

applied, slide the Style 10 Closure over 

the sprinkler and push the Closure over 

the Mounting Plate until it comes in 

contact with the wall mounting surface.

3

4

5

6

1
2

*

*

*

Temperature rating is

indicated on Deflector

Sealing

Assembly

Compression

Screw

Bulb

Deflector

Button

Frame

1/2"

NPT

WRENCH

FLATS

7/16"

(11,1 mm)

NOMINAL

MAKE-IN

1-1/2"

(38,1 mm)

2-3/16"

(55,6 mm)

ESCUTCHEON

PLATE SEATING

SURFACE

DEFLECTOR

HAT

1-13/16"

(46,0 mm)

9/16"

(14,3 mm)

CENTERLINE

OF SPRINKLER

WATERWAY

2-7/8" DIA.

(73,0 mm)

STYLE 10

RECESSED

ESCUTCHEON

-

-

-

-

-

-

6

4

2

5

3

1

FIGURE 6 

POLY-STAINLESS SERIES TY-FRB QUICK RESPONSE HORIZONTAL 

SIDEWALL (TY3331) 5.6 K-FACTOR 1/2 INCH NPT SPRINKLERS

Summary of Contents for TY-FRB Series

Page 1: ...ent Sprinklers The upright and pendent sprinklers are standard coverage spray sprinklers available in either 5 6 or 8 0 K factor The recessed version is intended for use in areas with a finished ceiling The two piece Style 10 1 2 inch NPT or Style 40 3 4 inch NPT recessed escutcheons provide 1 2 inch 12 7 mm of recessed adjustment or 3 4 inch 19 1 mm of total adjustment from the flush pendent posi...

Page 2: ...ecognized by the applicable Listing or Approval agency for example the UL Listing is based on the requirements of NFPA 13 Only the Style 10 or 40 Recessed Escutcheon as applicable is to be used for recessed installation Model K Factor Response Type Temperature Rating Bulb Liquid Color Sprinkler Material Brass TY B 5 6 1 2 in NPT SR Upright TY3151 and Pendent TY3251 135 F 57 C Orange 1 2 3 155 F 68...

Page 3: ...6 F 141 C Blue TY FRB 8 0 3 4 in NPT QR Upright TY4131 and Pendent TY4231 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Recessed Pendent TY4231 See Figure 4 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue NOTES 1 UL Listed 2 C UL Listed 3 EAC Approved Installed with Style 10 1 2 NPT Recessed Escutcheon Installed with Style...

Page 4: ... 93 C Green 286 F 141 C Blue TY FRB 5 6 1 2 in NPT QR Horizontal Sidewall TY3331 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue Recessed Horizontal Sidewall TY3331 See Figure 6 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue NOTES 1 UL Listed 2 C UL Listed 3 EAC Approved Installed with Style 10 1 2 NPT Recessed Escutcheon T...

Page 5: ...55 6 mm ESCUTCHEON PLATE SEATING SURFACE STYLE 10 RECESSED ESCUTCHEON 4 6 5 1 3 2 2 7 8 73 0 mm DIA UPRIGHT CROSS SECTION PENDENT RECESSED PENDENT 3 1 5 4 2 6 Sealing Assembly Compression Screw Temperature rating indicated on Deflector Frame Bulb Button Deflector WRENCH FLATS ESCUTCHEON PLATE SEATING SURFACE 3 4 NPT 2 1 4 57 2 mm 1 9 16 39 7 mm 2 5 16 58 7 mm 1 2 12 7 mm NOMINAL MAKE IN STYLE 40 R...

Page 6: ... the sprinkler by under or over tightening the sprin kler Re adjust the position of the sprin kler fitting to suit UPRIGHT CROSS SECTION PENDENT RECESSED PENDENT 6 4 3 2 1 5 Temperature rating indicated on Deflector Sealing Assembly Compression Screw Frame Bulb Button Deflector WRENCH FLATS ESCUTCHEON PLATE SEATING SURFACE 3 4 NPT 2 1 4 57 2 mm 1 9 16 39 7 mm 2 5 16 58 7 mm 1 2 12 7 mm NOMINAL MAK...

Page 7: ...lar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2C With pipe thread sealant applied to the sprinkler threads hand tighten the sprinkler into the sprinkler fitting Step 3C Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench as shown in Figure 10 Apply the W Type 6 Sprinkler Wrench to the wrench ...

Page 8: ...m 2 1 4 DIA 57 2 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING 5 8 1 4 15 9 6 4 mm MOUNTING PLATE 1 8 3 2 mm CLOSURE 13 16 20 6 mm 1 5 16 33 3 mm 1 4 6 4 mm 3 4 19 1 mm TY4231 or TY4251 FIGURE 7 POLY STAINLESS SERIES TY B OR TY FRB RECESSED PENDENT 5 6 K FACTOR 1 2 INCH NPT SPRINKLER ASSEMBLY WITH TWO PIECE 3 4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON FIGURE 8 POLY STAINLESS SERIES TY B ...

Page 9: ...damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like must be replaced Also replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb For more informa tion see the Installation section Frequent visual inspections are rec ommended to be initially performed for corrosion resistant sprinklers ...

Page 10: ... Protection Association TEFLON is a trademark of The Chemours Company FC LLC 1467 Elmwood Avenue Cranston RI 02910 Telephone 1 401 781 8220 2022 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Reviews: