Page 1 of 10
AUGUST 2022
TFP682
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp682
Series TY-B and TY-FRB
Poly-Stainless Sprinklers
General
Description
The TYCO Series TY-B and TY-FRB
Poly-Stainless Sprinklers are corrosion
resistant sprinklers designed for use in
commercial occupancies where corro-
sive atmospheres may exist.
The series characteristics are as
follows:
TY-B Series
• 5 mm diameter heat sensitive glass
bulb
• Standard response (SR) rating
TY-FRB Series
• 3 mm diameter heat sensitive glass
bulb
• Quick response (QR) rating
Although corrosion resistant sprinklers
have passed the standard corrosion
tests of the applicable approval agen-
cies, the testing is not representative
of all possible corrosive atmospheres.
Consequently, it is recommended that
the end user be consulted with respect
to the suitability of this coating material
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and gas/
chemical velocity, should be consid-
ered, at a minimum, along with the cor-
rosive nature of the chemical to which
the sprinklers will be exposed.
Upright and Pendent Sprinklers
The upright and pendent sprinklers are
standard coverage spray sprinklers
available in either 5.6 or 8.0 K-factor.
The recessed version is intended for
use in areas with a finished ceiling.
The two-piece Style 10 (1/2 inch NPT)
or Style 40 (3/4 inch NPT) recessed
escutcheons provide 1/2 inch (12,7
mm) of recessed adjustment or 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position. The adjustment
provided by the recessed escutcheon
reduces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Horizontal Sidewall Sprinklers
The horizontal sidewall sprinklers are
designed for installation along a wall
or side of a beam and just beneath a
smooth ceiling. Sidewall sprinklers are
commonly used instead of upright and
pendent sprinklers due to aesthetics or
building construction considerations,
where piping across the ceiling is not
desirable.
A recessed version of the horizon-
tal sidewall sprinkler can be achieved
by using the Style 10 recessed
escutcheon.
NOTICE
The Series TY-B and TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY-B Standard Response
TY3151 Upright 5 6K, 1/2 in NPT
TY3251 Pendent 5 6K, 1/2 in NPT
TY4151 Upright 8 0K, 3/4 in NPT
TY4251 Pendent 8 0K, 3/4 in NPT
TY3351 HSW* 5 6K, 1/2 in NPT
TY-FRB Quick Response
TY3131 Upright 5 6K, 1/2 in NPT
TY3231 Pendent 5 6K, 1/2 in NPT
TY4131 Upright 8 0K, 3/4 in NPT
TY4231 Pendent 8 0K, 3/4 in NPT
TY3331 HSW* 5 6K, 1/2 in NPT
* = Horizontal Sidewall