Tyco STAR Model A Manual Download Page 8

SETTING PROCEDURE

The Model A Preaction Valve will not automatically reset
after an operation. It must be manually reset and it should
be restored to service as soon as possible. Any impair-
ment to the system must be promptly corrected in order
to maintain the integrity of the system.

NOTES

It is recommended that the individual responsible for plac-
ing the Model A Preaction Valve in service develop an
overall understanding of the system, prior to placing it in
operation. These instructions, as well as individual in-
structions for the dry pilot actuator, solenoid valve, man-
ual control station, switches, accelerator (if applicable),
and pressure maintenance device should be reviewed.

After placing a fire protection system in service, notify the
proper authorities and advise those responsible for moni-
toring proprietary and/or central station alarms.
The setting procedure is as follows:

1. Close the System Main Control Valve (Fig. 1), Differen-

tial Chamber Supply Control Valve (Fig. 7), Air Supply
Control Valve (Fig. 7), and, if applicable, the Accelerator
Control Valve (Fig. 8).

2. Operate (open) the Manual Control Station (Fig. 7) to as-

sure that the Model A Preaction Valve Differential Cham-
ber is vented.

3. Open the Main Drain Valve (Fig. 7), Low Body Drain

Valve (Fig. 7), end-of-line Inspector’s Test Connection,
and all auxiliary drains in the system piping. Check to
see that the drainage water will not cause damage or re-
sult in dangerous conditions.

NOTE

Do not open the Inspector’s Test Connection and auxiliary
drains if resetting after a system test; otherwise, system air
pressure will be relieved unnecessarily.

4. Inspect for and clear all ice plugs, where system piping

has been exposed to freezing conditions and when
there has been a flow of water into the system.

5. After water ceases to drain, close the Inspector’s Test

Connection, all auxiliary drains in the system piping, and
the Low Body Drain Valve. Leave the Main Drain Valve
open.

6. Clean out the Strainer (16 - Fig. 6) in the connection to

the Model A Preaction Differential Chamber. Reassem-
ble the Strainer after cleaning.

7. Remove the Handhole Cover (4 - Fig. 2) and then care-

fully clean the Water Seat Disc, Air Seat Disc, Seat
Ring, and Clapper (22, 24, 3, 9 - Fig. 2). Verify that the
Retaining Lever (21 - Fig. 2), as well as the Differential

STAR SPRINKLER INC.

Page 8

2-4.1.10

FIGURE 8

OPTIONAL DOUBLE INTERLOCK

ACCELERATOR TRIM (#3644)

—MINIMUM 35 PSI WATER SUPPLY REQUIRED—

FIGURE 9

OPTIONAL PRIMING AND PRIMING TEST TRIM (#3022)

A14

ACCELERATOR

BLEED-OFF VALVE

(NORMALLY

CLOSED)

ACCELERATOR

CONTROL VALVE

(NORMALLY

ACCELERATOR

PRESSURE

GAUGE

1/2 INCH NPT

ACCELERATOR

CONNECTION

TO SYSTEM,

& INSTALL 1/2 INCH NPT

PLUGS IN ELBOWS

TO DRIP
FUNNEL

DISCARD THIS NIPPLE

TO DRIP
FUNNEL

A6

A14

A12

A4

A8

A13

A9

A11

A8

A9

A10

A3

A1

A13

A14

A7

A14

OPEN)

REFER TO

INSTALLATION

STEP 6

A2

A5

A15

PRIMING

VALVE

(NORMALLY

CLOSED)

TO DRIP
FUNNEL

PRIMING

CUP

PLUGS

DISCARD

TEST

VALVE

(NORMALLY

CLOSED)

PRIMING

P1

P8

P3

P9

P2

P4

P5

P8

P6

P7

NO. DESCRIPTION . . . QTY.

PART

A1

Accelerator,
Model S430 . . . . . .

1

#1306

A2

250 lb. Air Pressure
Gauge . . . . . . . . .

1

#923431012

A3

1/4" Gauge Test Valve

1

#460051002

A4

1/4" Globe Valve

. . .

1

#460471002

A5

1/2" Angle Valve

. . .

1

#460481004

A6

1/2" Swing Check Valve
with 3/32" Orifice . . .

1

#524031004

A7

1/2" Y-Strainer . . . . .

1

#523531005

A8

1/4" Tube Connector .

2

CH

A9

1/4" Tube, 36" Long . .

2

CH

A10 1/4" Plug . . . . . . . .

1

CH

A11 1/2" x 1/4" Bushing . .

1

CH

A12 1/2" x 1/4" x 1/2" Tee .

1

CH

A13 1/4" x 1-1/2" Nipple . .

2

CH

A14 1/2" x 1-1/2" Nipple . .

4

CH

A15 1/2" x 3" Nipple . . . .

1

CH

CH: Common Hardware

NO. DESCRIPTION . . . QTY.

PART

P1

Priming Cup . . . . . .

1

#923461004

P2

1/4" Globe Valve

. . .

1

#460471002

P3

1/2" Globe Valve

. . .

1

#460471004

P4

1/4" Tube Connector .

1

CH

P5

1/4" Tube, 36" Long . .

1

CH

P6

1/2" x 1/4" Reducing
Elbow

. . . . . . . . .

1

CH

P7

1/4" x 1-1/2" Nipple . .

1

CH

P8

1/2" x 1-1/2" Nipple . .

2

CH

P9

1/2" x 6" Nipple . . . .

1

CH

CH: Common Hardware

OBSOLETE

Summary of Contents for STAR Model A

Page 1: ...alve in a se ries configuration is utilized The double seat design of the Model A Preaction Valve isolates the system air pres sure which holds the Dry Pilot Actuator closed The Sole noid Valve remains closed until it is electrically energized by a releasing panel that is operated by either an electric fire detection device or electric manual pull station As an option for water supplies of 35 psi ...

Page 2: ...ainer 1 5596 21 Retaining Lever 1 5621 22 Water Seat Disc 1 5634 23 Disc Retaining Ring 1 5637 24 Air Seat Disc 1 5827 25 Differential Valve Housing 1 5573 26 Differential Valve Housing Gasket 2 5577 27 Differential Valve Housing Cover 1 5574 28 Differential Valve Housing Cover Bolt 5 8 11UNC x 3 1 2 4 1020 27 29 Roll Pin 2 1893 02 30 Differential Valve Seat 1 NR 31 Differential Valve Plunger 1 55...

Page 3: ...MBLY CLAPPER 04 07 05 ASSEMBLY RESTRICTOR LOCATED VALVE ON BACK OF NEUTRAL CHAMBER VALVE PLUNGER ASSEMBLY DIFFERENTIAL CAUTION LATCH POSITION SECOND LATCH CLAPPER LATCH FIRST POSITION REFER TO SETTING PROCEDURE STEP 8 01 08 PUSH HERE TO UNLATCH CLAPPER 02 LEVER RETAINING ENGAGED CLAPPER ARM 03 WATER SUPPLY PRESSURE DIFFERENTIAL CHAMBER SUPPLY DIFFERENTIAL CHAMBER VENT PORT IDENTIFICATION MAIN DRAI...

Page 4: ... pressure in the Differential Chamber is reduced to approximately one fifth of the water supply pressure Opening of both the Solenoid Valve and Dry Pilot Actua tor or operating the Manual Control Station will release water from the Model A Preaction Valve Differential Cham ber faster than it can be replenished through the 3 32 inch 2 4 mm diameter orifice of the Restrictor Assembly A rapid pressur...

Page 5: ... test or performing a system trip test Installation configuration and clearance dimensions are given in Figure 10 The flanged inlet and outlet connec tions are faced and drilled per ANSI Standard B16 1 un less otherwise specified when ordered In order to readily perform the System Inspection Proce dure described in the Maintenance and Service section it is recommended that a System Shut Off Valve ...

Page 6: ...lve S410 1 1133 1 13 1 2 Ball Valve 1 923001002 NO DESCRIPTION QTY PART 14 1 2 Globe Valve 1 460471004 15 1 2 Swing Check Valve 1 460491004 16 1 2 Y Strainer 1 523531005 17 1 2 Spring Loaded Check Valve 1 923221002 18 3 4 Swing Check Valve with 3 32 Orifice 1 524031005 19 1 1 2 Angle Valve 1 460481008 20 Drip Funnel Support Plug 1 922111005 21 Drip Funnel Support 1 922111003 22 Drip Funnel 1 92343...

Page 7: ...ressure setting After verifying the desired pres sure setting tighten the jam nut 9 Suitable provision must be made for disposal of drain water Drainage water must be directed such that it will not cause damage or result in dangerous conditions 10 All conduit and electrical connections are to be made in accordance with the requirements of the Authority Hav ing Jurisdiction and or the National Elec...

Page 8: ...drain close the Inspector s Test Connection all auxiliary drains in the system piping and the Low Body Drain Valve Leave the Main Drain Valve open 6 Clean out the Strainer 16 Fig 6 in the connection to the Model A Preaction Differential Chamber Reassem ble the Strainer after cleaning 7 Remove the Handhole Cover 4 Fig 2 and then care fully clean the Water Seat Disc Air Seat Disc Seat Ring and Clapp...

Page 9: ... also be replaced 12 Service the air dryer if applicable in accordance with the manufacturer s instructions 13 Open energize the Solenoid Valve Fig 7 by manually operating the releasing panel 14 Open the Differential Chamber Supply Control Valve Fig 7 and allow water to discharge from the Dry Pilot Actuator 15 Close the operating lever of the Manual Control Station Fig 7 Close the hinged cover and...

Page 10: ...l station alarms The Model A Preaction Valve is now set for service MAINTENANCE AND SERVICE The Model A Preaction Valve requires regularly sched uled maintenance and service In addition it is recom mended that the proper operation of the system and con dition of the system in which it is utilized be periodically verified in accordance with the following described inspec tion procedure Any impairme...

Page 11: ...edure section SERVICE RECOMMENDATIONS Drop In Water Supply Pressure Below Normal Range NOTE If the water supply pressure is significantly reduced be low the normally expected static pressure range as could occur in the case of a water main break or repair and there is a subsequent drop in the differential cham ber water pressure below its normal range due for exam ple to a leak in a piping connect...

Page 12: ...ntial Valve Plunger Assembly is accomplished by varying the thread engagement be tween the Plunger Nose and the Plunger Start with an overall assembly length of 4 7 8 inches and then insert the Differential Valve Assembly into the Differential Valve Seat With the Clapper Assembly seated and while pulling the Retaining Lever from left to right push the Differential Valve Plunger Assembly completely...

Reviews: