The drain tubing must be installed with smooth bends
that will not restrict flow.
The connection to the system piping must be located on
the supply side of the System Shut-off Valve (Fig. 1)
and at least two feet above the Model A Preaction
Valve, so that drain back/condensate will not flow into
the Accelerator piping.
Connections to a feed or cross main must be made
either to the side or top of the main.
After installing the S430 Accelerator, close the Accelera-
tor Control Valve.

NOTES

Failure to follow the above instructions can result in accidental
tripping of the Accelerator.
The Accelerator Control Valve must be closed during hydro-
static testing of the system to prevent internal damage to the
S430 Accelerator.

7. The Low Air Pressure Alarm Switch (7 - Fig. 6) is to be

adjusted to operate on falling pressure at approximately

6 psi (0.4 bar) below the minimum Double Interlock Dry
System air pressure requirement shown in Figure 5.

8. The Pressure Relief Valve (10 - Fig. 6) is factory set to

relieve at a pressure of approximately 45 psi (3.1 bar),
which can typically be used for a maximum system pres-
sure of 40 psi (2.8 bar). The Pressure Relief Valve may
be adjusted; however, it must be adjusted to relieve at a
pressure which is in accordance with the requirements
of the Authority Having Jurisdiction.
To adjust the Pressure Relief Valve, first loosen the jam
nut and then adjust the cap accordingly — clockwise for
a higher pressure setting or counterclockwise for a
lower pressure setting. After verifying the desired pres-
sure setting, tighten the jam nut.

9. Suitable provision must be made for disposal of drain

water. Drainage water must be directed such that it will
not cause damage or result in dangerous conditions.

10. All conduit and electrical connections are to be made in

accordance with the requirements of the Authority Hav-
ing Jurisdiction and/or the National Electrical Code.

STAR SPRINKLER INC.

2-4.1.10

Page 7

FIGURE 7

3 INCH (DN80) ELECTRIC/PNEUMATIC DOUBLE INTERLOCK PREACTION TRIM

SUB-ASSEMBLIES (#3008)

AIR SUPPLY

CONTROL VALVE

AUTOMATIC

DRAIN VALVE

CONTROL

STATION

MANUAL

PRESSURE

GAUGE

AIR SUPPLY

SYSTEM

PRESSURE

GAUGE

SUPPLY

WATER

CLOSED)

DRAIN VALVE

(NORMALLY

LOW BODY

CLOSED)

(NORMALLY

ACTUATOR

(NORMALLY

OPEN)

PRESSURE

GAUGE

DIFFERENTIAL

CHAMBER

PRIMING TRIM

FOR OPTIONAL

CONNECTION

1/2 INCH NPT

(SEE FIGURE 8)

ACCELERATOR TRIM

FOR OPTIONAL

TEST VALVE

ALARM

(NORMALLY

CLOSED)

PRESSURE

LOW AIR

ALARM

CONNECTIONS

1/2 INCH NPT

SWITCH

1/2 INCH NPT

CONNECTION

FOR SYSTEM

AIR SUPPLY

DRY PILOT

1/4"x10"

(REF.)

E

F

G

H

SYSTEM

ASSEMBLY "H"

AS SHOWN

INSTALL

(SEE FIGURE 9)

CLOSED)

(NORMALLY

DRAIN VALVE

MAIN

FUNNEL

DRIP

*

*

*

INCH NPT
TO DRAIN

1-1/2

INCH

NPT TO

1-1/4

15°

DRAIN

A

B

CONTROL VALVE

(NORMALLY

1/2 INCH NPT

FROM WATER

SUPPLY

DIFFERENTIAL

CHAMBER SUPPLY

OPEN)

C

MOTOR ALARM

FOR WATER

CONNECTION

3/4 INCH NPT

D

PRESSURE

WATERFLOW

ALARM SWITCH

*

*

NOTES:

1. SEE FIGURE 3 FOR PORT IDENTIFICATION.

PORT "07" MUST VENT TO ATMOSPHERE

2.

FOR PROPER VALVE OPERATION.

ASSEMBLE IN ALPHABETICAL ORDER.

3.

ROUTE ALL TUBING TO DRIP FUNNEL.

*

(SEE FIGURE 7)

PRIMING TRIM

FOR OPTIONAL

CONNECTION

1/2 INCH NPT

SEPARATELY

ORDERED

VALVE,

SOLENOID

CLOSED)

(NORMALLY

OBSOLETE

Summary of Contents for STAR Model A

Page 1: ...alve in a se ries configuration is utilized The double seat design of the Model A Preaction Valve isolates the system air pres sure which holds the Dry Pilot Actuator closed The Sole noid Valve remains closed until it is electrically energized by a releasing panel that is operated by either an electric fire detection device or electric manual pull station As an option for water supplies of 35 psi ...

Page 2: ...ainer 1 5596 21 Retaining Lever 1 5621 22 Water Seat Disc 1 5634 23 Disc Retaining Ring 1 5637 24 Air Seat Disc 1 5827 25 Differential Valve Housing 1 5573 26 Differential Valve Housing Gasket 2 5577 27 Differential Valve Housing Cover 1 5574 28 Differential Valve Housing Cover Bolt 5 8 11UNC x 3 1 2 4 1020 27 29 Roll Pin 2 1893 02 30 Differential Valve Seat 1 NR 31 Differential Valve Plunger 1 55...

Page 3: ...MBLY CLAPPER 04 07 05 ASSEMBLY RESTRICTOR LOCATED VALVE ON BACK OF NEUTRAL CHAMBER VALVE PLUNGER ASSEMBLY DIFFERENTIAL CAUTION LATCH POSITION SECOND LATCH CLAPPER LATCH FIRST POSITION REFER TO SETTING PROCEDURE STEP 8 01 08 PUSH HERE TO UNLATCH CLAPPER 02 LEVER RETAINING ENGAGED CLAPPER ARM 03 WATER SUPPLY PRESSURE DIFFERENTIAL CHAMBER SUPPLY DIFFERENTIAL CHAMBER VENT PORT IDENTIFICATION MAIN DRAI...

Page 4: ... pressure in the Differential Chamber is reduced to approximately one fifth of the water supply pressure Opening of both the Solenoid Valve and Dry Pilot Actua tor or operating the Manual Control Station will release water from the Model A Preaction Valve Differential Cham ber faster than it can be replenished through the 3 32 inch 2 4 mm diameter orifice of the Restrictor Assembly A rapid pressur...

Page 5: ... test or performing a system trip test Installation configuration and clearance dimensions are given in Figure 10 The flanged inlet and outlet connec tions are faced and drilled per ANSI Standard B16 1 un less otherwise specified when ordered In order to readily perform the System Inspection Proce dure described in the Maintenance and Service section it is recommended that a System Shut Off Valve ...

Page 6: ...lve S410 1 1133 1 13 1 2 Ball Valve 1 923001002 NO DESCRIPTION QTY PART 14 1 2 Globe Valve 1 460471004 15 1 2 Swing Check Valve 1 460491004 16 1 2 Y Strainer 1 523531005 17 1 2 Spring Loaded Check Valve 1 923221002 18 3 4 Swing Check Valve with 3 32 Orifice 1 524031005 19 1 1 2 Angle Valve 1 460481008 20 Drip Funnel Support Plug 1 922111005 21 Drip Funnel Support 1 922111003 22 Drip Funnel 1 92343...

Page 7: ...ressure setting After verifying the desired pres sure setting tighten the jam nut 9 Suitable provision must be made for disposal of drain water Drainage water must be directed such that it will not cause damage or result in dangerous conditions 10 All conduit and electrical connections are to be made in accordance with the requirements of the Authority Hav ing Jurisdiction and or the National Elec...

Page 8: ...drain close the Inspector s Test Connection all auxiliary drains in the system piping and the Low Body Drain Valve Leave the Main Drain Valve open 6 Clean out the Strainer 16 Fig 6 in the connection to the Model A Preaction Differential Chamber Reassem ble the Strainer after cleaning 7 Remove the Handhole Cover 4 Fig 2 and then care fully clean the Water Seat Disc Air Seat Disc Seat Ring and Clapp...

Page 9: ... also be replaced 12 Service the air dryer if applicable in accordance with the manufacturer s instructions 13 Open energize the Solenoid Valve Fig 7 by manually operating the releasing panel 14 Open the Differential Chamber Supply Control Valve Fig 7 and allow water to discharge from the Dry Pilot Actuator 15 Close the operating lever of the Manual Control Station Fig 7 Close the hinged cover and...

Page 10: ...l station alarms The Model A Preaction Valve is now set for service MAINTENANCE AND SERVICE The Model A Preaction Valve requires regularly sched uled maintenance and service In addition it is recom mended that the proper operation of the system and con dition of the system in which it is utilized be periodically verified in accordance with the following described inspec tion procedure Any impairme...

Page 11: ...edure section SERVICE RECOMMENDATIONS Drop In Water Supply Pressure Below Normal Range NOTE If the water supply pressure is significantly reduced be low the normally expected static pressure range as could occur in the case of a water main break or repair and there is a subsequent drop in the differential cham ber water pressure below its normal range due for exam ple to a leak in a piping connect...

Page 12: ...ntial Valve Plunger Assembly is accomplished by varying the thread engagement be tween the Plunger Nose and the Plunger Start with an overall assembly length of 4 7 8 inches and then insert the Differential Valve Assembly into the Differential Valve Seat With the Clapper Assembly seated and while pulling the Retaining Lever from left to right push the Differential Valve Plunger Assembly completely...

Reviews: